391 fire alarm terms from the NICET Fire Alarm Systems content outlines and the practice questions, with short definitions. Many have a formal definition in NFPA 72 Chapter 3: knowing the exact term helps you find it in the index of your printed code.

0.7S rule
Layout check that every point on the ceiling is within 0.7 times the spacing of a detector (21 ft for 30 ft smoke spacing).
Abandoned equipment
Fire alarm equipment no longer in use. NFPA 72-2022 requires it to be removed and to be marked "not in service" until it is removed.
Abandoned fire alarm cable
Cable not terminated at equipment and not identified for future use with a tag; its accessible portion must be removed.
Above finished floor (AFF)
The reference for mounting heights, measured from the finished floor.
Accessory occupancy
A minor use, generally no more than 10% of the story area, that follows the main occupancy (Section 508.2).
Acoustically distinguishable space (ADS)
Zone or subdivision with its own acoustic characteristics in which voice intelligibility is planned and evaluated.
Action level
Exposure that triggers measures such as monitoring or conservation programs (for example, 85 dBA for noise).
ADDIE
Instructional design model: Analysis, Design, Development, Implementation, Evaluation.
Addressable device
Component with its own identification whose status can be individually identified or that individually controls functions.
Affected employee
A person who operates or works near the locked-out equipment; must be notified before and after the lockout.
AHJ
Authority having jurisdiction: the organization or person that enforces the code or approves the installation.
Air sampling (aspirating) detector
System that draws air through a network of pipes with sampling holes and analyzes it at a central detector.
Air-sampling detector
System that draws air through pipes with sampling ports to a central detector; ports count as spot detectors.
Air-sampling-type detector
A system that draws air through a network of sampling pipes to a central detector; each sampling port counts as a spot-type detector.
Alarm load
Current the system draws with the alarm notification appliances operating; it is carried for 5 minutes (15 for voice) in the battery calculation.
Alarm signal
Signal that results from the manual or automatic detection of an alarm condition.
Alarm verification
Feature that resets a smoke detector and confirms the alarm before reporting it; limited to 60 s.
Alarm verification feature
Feature that requires smoke detectors to confirm the condition for a period, or after a reset, to reduce unwanted alarms.
Alternating current (ac)
Current that periodically reverses direction; 60 Hz in the U.S.
Ambulatory care facility
A Group B facility giving outpatient care that can leave patients unable to save themselves; it triggers a fire alarm system regardless of load.
Amended construction documents
Revised documents submitted for approval when changes during construction depart from the approved set.
Ampere-hour (Ah)
Battery capacity: the current multiplied by the time the battery can deliver it.
Analog value
Numeric reading a detector sends the panel; a value far above its neighbors suggests contamination.
Approved
Acceptable to the AHJ.
Approved as Noted
A review action that lets work proceed with the reviewer's corrections; Revise and Resubmit does not.
Architect / engineer
The design professional who administers the contract, reviews submittals, answers RFIs, and certifies payment and Substantial Completion.
Assured equipment grounding conductor program (AEGCP)
Written alternative to GFCIs on construction sites: daily inspection and continuity and connection tests every ≤ 3 months.
Atrium
A vertical opening through floors, closed at the top, other than stairs, elevators or shafts; the fire alarm trigger of Section 907.2.14 applies when it connects more than two stories.
Attendant
Person who stays outside the confined space, monitors the entrants, and summons rescue.
Authority Having Jurisdiction (AHJ)
Organization, office, or individual responsible for enforcing the code or approving equipment, materials, installations, or procedures.
Authorized employee
The person who applies lockout/tagout to service or maintain the equipment.
Automated external defibrillator (AED)
Device that analyzes the heart rhythm and delivers a shock if needed.
Average ambient sound level
The A-weighted RMS level measured over the period when people are present, or 24 hours, whichever is less.
Barrier
Fixed divider that allows PLFA and power conductors in the same enclosure (760.136(B)).
Baseline ohmic value
The reading recorded on each battery cell/unit when installed (or supplied by the manufacturer) and used for later comparison.
Beam pocket
The ceiling area between two beams; deep beams may require a smoke detector in each pocket.
Bid bond
Surety guarantee that the bidder will sign the contract and furnish required bonds if awarded.
Box fill
Calculation of the minimum box volume based on the conductors and devices it contains (314.16).
Branch circuit
Conductors between the final overcurrent device and the outlets; the FACU branch circuit must not supply other loads.
Cable substitution
Using a cable with equal or better fire performance in place of the one required, per Table 760.154(A).
Cable tie
Cable fastener; nonmetallic ties used in plenums must be listed for low smoke and heat release.
Candela (cd)
Unit of effective light intensity used to rate visible notification appliances.
Capacity margin
Factor applied to the calculated ampere-hours to allow for battery aging (1.25 in the 2022 edition per industry summaries).
Ceiling-height multiplier
Factor from Table 17.6.3.5.1 that reduces heat detector spacing on ceilings between 10 and 30 ft.
Central / proprietary / remote supervising station
Types of stations that receive signals away from the protected premises (Ch. 26).
Central station
A listed supervising station providing central station service, including immediate retransmission of alarms.
Certificate of occupancy
The building official's authorization to occupy a building; a temporary certificate may cover a portion that can be occupied safely (IBC §111).
Change order
A document that authorizes a change in the contract's scope, cost, or schedule.
Circuit integrity (CI) cable
Cable rated to keep a circuit operating for a period (1 or 2 h) under fire conditions.
Circular mil (cmil)
Unit of conductor area used in NEC Table 8 (14 AWG = 4110 cmil).
Claim
Demand by Owner or Contractor for an adjustment of terms, payment of money, or extension of time; notice within 21 days (A201-2017 §15.1.3.1).
Class A / X pathway
Redundant pathway that tolerates a single open; Class X also tolerates a short.
Class D pathway
A fail-safe pathway: loss of the pathway causes the intended function to occur.
Common path of egress travel
Part of the exit access travel distance before occupants have separate access to two exits or exit access doorways.
Compatibility listing
Manufacturer and listing information showing which devices may be connected to a given control unit circuit.
Compensatory measure
Alternative means, such as a person at a manual control, that performs a function while the automatic function is out of service.
Competent person
Person capable of identifying existing and predictable hazards and authorized to take prompt corrective measures (1926.32(f)).
Concretetight fitting
EMT coupling or connector made so that concrete cannot enter the raceway; required where EMT is embedded in concrete.
Conduit fill
Percentage of a raceway's interior area occupied by conductors or cables (NEC Ch. 9, Table 1).
Conflict of interest
Situation in which a personal interest could influence, or appear to influence, professional judgment; disclose it in writing when it cannot be avoided.
Construction Change Directive (CCD)
Order signed by owner and architect directing a change before price or time is agreed.
Control capability
Ability of a detector with a control output to operate its relay even when other devices on the same circuit are in alarm.
Control valve supervisory switch (tamper)
Sends a supervisory signal when the valve is closed; must operate within 2 revolutions or 1/5 of the travel.
Correction factor (battery)
The 1.25 multiplier NFPA 72-2022 applies to the calculated amp-hours (the earlier editions used a 20 percent margin).
Cost-plus contract
Actual documented cost plus a fee for overhead and profit.
Crashing
Adding resources to critical-path activities to shorten the schedule, at added cost; take the lowest cost per day first and re-check the network.
Critical path
The longest chain of dependent activities; it sets the project duration and has zero float.
Critical path and float
The longest chain of dependent tasks sets the project length; float is how far a task can slip without delaying the finish.
Current (I)
Flow of electric charge, measured in amperes (A) with the ammeter in series.
DACT
Digital alarm communicator transmitter: dials the supervising station over a telephone line and requires a second transmission means.
dBA
A-weighted sound level in decibels, the measure used for audibility requirements.
Dedicated branch circuit
Branch circuit that supplies only the fire alarm system; required for the primary power supply (§10.6.5.1).
Deferred submittal
A portion of the design, such as fire alarm shop drawings, submitted after the permit with prior approval (Section 107.3.4.1).
Deficiency
A condition that affects system performance; it must be corrected and, if not corrected at the end of the visit, reported in writing within 24 h.
Delayed-egress locking system
Lock that delays door release for a short period after the release device is pushed and an alarm sounds.
Designated level / alternate level
Floors to which elevators are sent on Phase I recall, depending on which detector operates.
Designated representative
Person or company to whom the owner assigns ITM responsibility by contract or lease.
Device schedule
Table listing each device with type, location, address, and settings such as candela.
Disconnecting means
Device that disconnects a circuit from its source; for fire alarm it has red identification and is labeled 'FIRE ALARM CIRCUIT'.
Documentation cabinet
A cabinet labeled SYSTEM RECORD DOCUMENTS where the record documentation is stored (§7.7.2).
Double-action manual box
A manual fire alarm box that needs two motions, such as lifting or pushing a cover and then pulling the handle.
Drift compensation / maintenance alert
Feature that adjusts the detector for accumulated dirt and warns when it needs cleaning.
Duct smoke detector
A detector listed to sample the air inside an HVAC duct, used to control the spread of smoke.
Duplicate address
Trouble that occurs when two devices on an SLC have the same address.
Duty rating
Maximum ladder load (person + tools + material): IAA 375, IA 300, I 250, II 225, III 200 lb.
Earned value (EV)
Budgeted value of the work actually performed; CPI = EV ÷ AC and SPI = EV ÷ PV.
ECF interface device
The fire alarm system component that connects to an emergency control function, such as the relay that recalls an elevator.
Effective ground-fault current path
Low-impedance path that allows the overcurrent device to operate; the earth is not considered one.
Effective intensity (candela)
The light output rating of a visible notification appliance used in the room spacing tables.
Effective intensity (cd)
The luminous intensity of a flashing light expressed as an equivalent steady light; it is the cd value used in the spacing tables.
Electrical metallic tubing (EMT)
Thin-wall metal raceway; FPL and FPLR are permitted inside it in plenums (Table 760.154).
Emergency control function (ECF)
A building safety function started by the fire alarm system, such as elevator recall, fan shutdown, or door release.
Emergency control function interface device
Relay or module that connects the FACU to elevators, HVAC, doors, etc.; within 3 ft of the controlled component (§21.2.4).
Emergency impairment
Unplanned loss of a system, component, or function, for example from lightning, fire, or flood.
Emergency voice/alarm communication system (EVACS)
A system that gives spoken evacuation instructions (Section 907.5.2.2), required for example in high-rises and large assembly.
End-of-discharge voltage
Lowest battery voltage at which the panel still operates, about 20.4 V on a 24 V system; the worst-case starting voltage.
End-of-line (EOL) resistor
A resistor at the end of a Class B circuit that lets the panel supervise the continuity of the wiring.
End-of-line device (EOL)
A resistor or other device at the end of a Class B circuit that allows the wiring to be monitored for integrity.
Energy-isolating device
Breaker, disconnect, or valve that physically prevents the transmission of energy; a push button is not one.
EOL resistor
Resistor at the last device that lets the panel supervise a Class B circuit.
Equipment grounding conductor (EGC)
Conductor that connects the metal parts of equipment back to the source so ground faults are cleared.
Equivalency
Use of a system, method, or device of equivalent or superior effectiveness, shown by technical documentation and approved by the AHJ (§1.5).
Executive software
The control unit manufacturer's firmware or operating system; a change requires a 10% functional test.
Exhibit
A drawing, table, or diagram that accompanies an exam question.
Exit
Portion of the means of egress between the exit access and the exit discharge, such as an enclosed interior exit stairway.
Exit access
Portion of the means of egress that leads from any occupied space to an exit (rooms, aisles, corridors).
Exit discharge
Portion of the means of egress between the end of an exit and a public way.
Exit marking audible notification appliance
A directional sounder that guides occupants to exits and areas of refuge (§18.4.8).
Exposing employer
An employer whose employees are exposed to a hazard it did not create (OSHA multi-employer policy).
F rating
Time a through-penetration firestop system resists flame passage in the standard fire test.
F rating / T rating
F: time the system blocks flame passage. T: time before the unexposed side rises 325 degrees F; T is also required in floors.
Fast tracking
Overlapping activities that were planned in sequence to shorten the schedule; it raises rework risk.
Fault isolation module
SLC device that isolates a shorted segment so the rest of the loop keeps operating.
Fault isolator
Device that separates a shorted section so the rest of the SLC keeps operating (Class X).
Field of view
The area an observer can see from one position; it determines whether strobes must be synchronized.
Fire alarm circuit
The portion of the wiring and connected equipment powered and controlled by the fire alarm system; PLFA or NPLFA.
Fire alarm control unit (FACU)
Component with primary and secondary power that receives signals from initiating devices or other control units and processes them to operate the required outputs.
Fire area
The floor area enclosed by fire walls, fire barriers, horizontal assemblies or exterior walls, used for sprinkler thresholds.
Fire barrier
A fire-resistance-rated wall assembly (Section 707) that continues through concealed spaces to the deck above.
Fire command center
A rated room, required in high-rises, that houses the annunciator, voice alarm control and other fire department controls (Section 911).
Fire damper / smoke damper
Dampers in ducts at rated walls or smoke barriers (Section 717); smoke dampers close on a signal from a smoke detector.
Fire warden
Building staff member or tenant trained to perform assigned duties during a fire emergency.
Fire watch
Approved mitigating measure: personnel who patrol the building while the system is out of service.
Firestop
Listed system that seals a penetration of a fire-rated assembly so the rating is maintained.
Firestopping
Approved sealing of penetrations in fire-resistance-rated walls, floors, or ceilings (300.21).
Fixed-temperature detector
Responds when its sensing element reaches a preset temperature (for example, 135°F or 194°F).
Float
How long an activity can slip without delaying the project.
Free fall
Distance a person falls before the system starts to slow the fall; 6 ft maximum.
Free float
Time an activity can slip without delaying the early start of any successor.
General contractor
The prime contractor responsible for supervising and coordinating all trades and for jobsite safety.
Graphic (bar) scale
A bar drawn on the sheet that stays valid even when the drawing is printed reduced.
Gross margin
Profit as a percentage of the selling price: price = cost ÷ (1 − margin).
Ground fault
Unintended connection of a circuit conductor to ground (conduit, box, structure).
Ground-fault circuit interrupter (GFCI)
Device that opens the circuit when it detects leakage current to ground; protects people from shock.
Guardrail system
Top rail, midrail, and posts that prevent falls from an edge.
Half-splitting
Troubleshooting technique that opens the circuit at its midpoint to eliminate the good half at each step.
Hard short
A direct, near-zero-ohm connection between two conductors.
High-rise building
A building with an occupied floor more than 75 ft above the lowest level of fire department vehicle access.
Hotspot item
A question answered by clicking on an area of the figure.
Impairment
Abnormal condition, planned or emergency, in which a system, component, or function is out of order.
Informational note
Explanatory NEC material that is not an enforceable requirement (90.5(C)).
Initial acceptance test
Inspection and test of a new system under Chapter 14, with the AHJ notified beforehand (§14.4.1).
Initiating device
Component that originates transmission of a change-of-state condition, such as a smoke detector, manual fire alarm box, or supervisory switch.
Initiating device circuit (IDC)
Circuit of initiating devices whose signal does not identify the individual device that operated.
Input/output matrix
A table showing which outputs each input produces; an accepted form of the sequence of operation (Figure A.14.6.1.1).
Inspection
Visual examination of equipment to verify its location and condition and that nothing has changed or been damaged (Table 14.3.1).
Inspector's test connection
Sprinkler system outlet that simulates the flow of one sprinkler to test the waterflow switch.
Insulation resistance test
High-voltage (megohmmeter) test of insulation between conductors and to ground; devices and panel must be disconnected.
Interface device
The relay or module that connects the fire alarm system to the equipment performing an emergency control function.
Inverse-square law
In free field, sound pressure level drops about 6 dB each time the distance doubles.
Ionization smoke detection
A principle that uses a small radioactive source to ionize the air; smoke reduces the ion current and causes an alarm.
KT (temperature factor)
Correction used in the battery load-test capacity calculation; 1.0 at 77°F (25°C).
L rating
Air leakage rating of a penetration firestop system in a smoke barrier.
Labeled
Bearing the label, symbol, or mark of an evaluation organization acceptable to the AHJ.
Lead time
Time from placing an order to delivery of the item; in scheduling software it can also mean an overlap between linked activities.
Legend
The table on a drawing that defines each symbol and abbreviation (symbols per NFPA 170).
Level of exit discharge
The story where an exit ends and the exit discharge begins; 'above or below' triggers are counted from it.
Lien waiver
Document releasing lien rights; a conditional waiver takes effect only when payment is received.
Line seizure
DACT ability to take over a telephone line from other equipment to send a signal.
Listed
Included in a list published by an organization acceptable to the AHJ that evaluates products and periodically inspects production.
Listed compatible
Evaluated by a testing laboratory for use with a specific control unit, not merely listed on its own.
Listed spacing
The maximum spacing between heat detectors determined by the listing laboratory and published by the manufacturer (the S value).
Lockout/tagout (LOTO)
Procedure to isolate energy with locks and tags and verify zero energy before work.
Loop resistance test
Measurement of a circuit pair with the far end shorted; the reading is compared with the manufacturer's limit and with the resistance calculated from the wire size and length.
Low-frequency signal (520 Hz)
An audible signal with a fundamental frequency of 520 Hz ±10 percent, required to awaken occupants in sleeping areas.
Lump sum contract
Fixed price; the contractor carries the cost-overrun risk.
Lumped load
Calculation method that assumes all NAC current is drawn at the last appliance; gives a conservative result.
Maintenance
Work done to keep equipment operable per the manufacturer's instructions (Section 14.5).
Manual fire alarm box
Manually operated device used to initiate an alarm signal (pull station).
Manual fire alarm box (pull station)
An initiating device operated by a person to send a fire alarm.
Manufacturer's published instructions
The installation, operation, and maintenance instructions that come with listed equipment.
Margin vs. markup
Margin is a percentage of the selling price (price = cost / (1 - margin)); markup is a percentage of cost.
Markup
Percentage added to cost to obtain the price: price = cost × (1 + markup).
Masked threshold (narrow band)
The minimum level at which a tone can be heard in the presence of noise; the alternate method requires exceeding it by 10 dB per octave band or 13 dB per one-third octave band.
Mass notification system (MNS)
A system that sends emergency messages for events other than fire, based on a risk analysis and an emergency response plan.
MasterFormat
The CSI numbering of specification sections in divisions; fire alarm is 28 31 00 in the 2004 edition and 28 46 00 in later ones.
Mechanic's lien
A claim against the owner's property by an unpaid contractor, subcontractor, or supplier.
Mechanical guard
Impact protection for a detector; it must be listed for use with that detector.
Megohmmeter (insulation tester)
Instrument that applies a high dc voltage to measure insulation resistance in MΩ.
Membrane penetration
An opening in only one face of a rated wall, such as an outlet box; the IBC limits box size, total area and back-to-back placement.
Minimum hearing distance
The closest distance an occupant's ear can be to an audible appliance; the 110 dBA maximum applies there (new definition in 2022).
Mitigating measures
Steps during an impairment, such as a fire watch, that the AHJ may require.
Mitigation plan
Plan naming who contacts the communications center if a real alarm occurs during remote programming of transmitters.
Mixed occupancy (NFPA 101)
Occupancies so intermingled that separate safeguards are impracticable; the most restrictive requirements apply.
Modification
After signing, a written amendment, Change Order, Construction Change Directive, or architect's minor-change order.
Monitoring for integrity
Automatic detection of opens and ground faults on conductors, annunciated within 200 s (§12.6.1).
Multi-candela (selectable) appliance
A strobe with a switch or jumper to choose the intensity (for example, 15, 30, 75, 95, 110 cd); set it per the approved drawings.
Multimeter (DMM)
Instrument that measures voltage, current, and resistance depending on the function and inputs selected.
NAC power extender
Remote power supply that powers additional NACs; requires its own secondary supply.
Neat and workmanlike manner
Quality of workmanship required by 110.12 and 760.24(A): cables orderly, supported, and undamaged.
NFPA 3 and NFPA 4
NFPA 3 covers the commissioning process; NFPA 4 covers integrated testing of interconnected fire protection and life safety systems.
Nipple
Short length of conduit (24 in. or less) between boxes or enclosures; may be filled to 60%.
Nominal spacing
For spot-type smoke detectors on smooth ceilings, 30 ft (9.1 m) between detectors.
Non-power-limited fire alarm (NPLFA) circuit
Circuit powered by a source that complies with 760.41 and 760.43, up to 600 V; Parts I and II.
Nonrestorable heat detector
Detector whose sensing element is destroyed when it operates; it is not heat tested in the field.
Nonseparated occupancies
Mixed uses with no rated separation; the most restrictive Chapter 9 provisions apply to the total area (Section 508.3).
Normally open (N.O.) contact
A contact that is open at rest and closes when the device operates; the usual alarm contact of conventional initiating devices.
Notification appliance
A component (horn, strobe, speaker, etc.) activated by the system that alerts occupants with audible, visual, tactile, or textual output.
Notification appliance circuit (NAC)
Circuit directly connected to notification appliances such as horns, strobes, or speakers.
Notification appliance control circuit (NACC)
Circuit from a control unit or module that switches or controls notification appliances; when supervised it serves no more than one notification zone.
Notification zone
A defined area in which occupant notification is accomplished simultaneously.
Nuisance alarm
Unwanted activation caused by a non-hazardous stimulus or condition (steam, dust, cooking smoke).
Observation
A suggested improvement that is neither an impairment nor a deficiency; the owner is not required to act on it (new in 2022).
Occupancy group
The IBC classification of a building by use (A, B, E, F, H, I, M, R, S, U) that drives fire alarm, sprinkler and construction requirements.
Occupant load
The number of persons a space is designed for, found by dividing floor area by the Table 1004.5 factor for the use.
Occupant load factor
Floor area per person (gross or net) that the code assigns to a use, such as 7 ft² net for concentrated assembly.
Ohm's law
The relationship E = I × R between voltage, current, and resistance.
Ohmic test
Measurement of a battery's internal conductance, resistance, or impedance, compared with a baseline value.
Open / ground fault / short circuit
The three basic wiring faults; the pathway class defines which ones the circuit tolerates.
Open circuit
A break in the current path; the ohmmeter reads OL (infinite).
Open-grid ceiling
A ceiling of louvers or egg-crate material with large openings; detectors may be omitted below it only if the opening size, thickness, and 70 percent open-area conditions are all met.
Optical fiber cable (OFNP/OFNR/OFN)
Cable installed per Article 770; OFNP for plenums, OFNR for risers, OFN/OFNG for general use.
Other space used for environmental air (plenum)
Space, such as above a return-air suspended ceiling, that forms part of the air-handling system (300.22(C)).
Out of service
In the NFPA 101 annex, a significant portion of the system is not functioning (for example a whole circuit), not a single device or appliance.
Overcurrent protective device (OCPD)
Breaker or fuse that protects the conductors; for the FACU circuit, its location is identified at the FACU.
Owner
The party that pays for the project and contracts with the general contractor.
Owner's manual
Narrative, sequence of operation, operator instructions, maintenance and testing description, service directory, and data sheets delivered with a new system (§7.5.4).
Parallel circuit
Several branches with the same voltage; branch currents add (like the appliances on a NAC).
Pathway
Medium (wire, fiber, radio) that connects system equipment; its performance is designated by class (Ch. 12).
Pathway class
NFPA 72 designation (A, B, C, D, E, N, X) of how a pathway is monitored and what faults it tolerates.
Pathway class (A / B)
Class A has a redundant path and keeps operating with an open; Class B does not, and loses everything beyond the open.
Pathway class designation
The circuit class (A, B, X, etc.) per 12.3; shown on the drawings with the EOL location.
Pathway survivability
Ability of a pathway to keep operating during a fire; Levels 0 to 4 (§12.4).
Pathway survivability level
Designation (0 to 4) describing protection of a pathway against fire damage, such as sprinklers with metal raceway or 2-hour cable.
Payment bond
Guarantees that subcontractors and suppliers will be paid.
Performance and payment bonds
Surety guarantees that the contractor will complete the contract and that subcontractors and suppliers will be paid.
Performance bond
Guarantees that the contractor will complete the contract.
Performance-based design
A design justified by goals, criteria, and analysis rather than by prescriptive spacing or layout rules; accepted by the AHJ.
Performance-based technologies
IP or cellular communication to the supervising station (§26.6.3).
Periodic frequency
How often a component is inspected (Table 14.3.1) or tested (Table 14.4.3.2): weekly, monthly, quarterly, semiannually, annually, or at a multi-year interval; count the interval from the date of the last inspection or test.
Periodic testing
Recurring testing at the Table 14.4.3.2 frequency, whose purpose is to assure operational reliability.
Permanent records
Reproducible as-built drawings, O&M manuals, written sequence of operation, and software documentation, kept for the life of the system.
Permissible exposure limit (PEL)
Maximum legal exposure, usually as an 8-hour time-weighted average (TWA).
Permit-required confined space
Confined space with a hazardous atmosphere, engulfment or entrapment hazard, or other serious hazard.
Personal fall arrest system (PFAS)
Anchorage, connector, and full-body harness that stop a fall in progress.
Phase I recall
Elevators return to the designated level (or alternate level), open their doors, and leave normal service.
Phase II
Firefighters' in-car elevator operation with a key switch, after Phase I recall.
Photoelectric light-scattering detection
Smoke entering the chamber scatters light onto a photosensor; responds well to smoldering fires with large particles.
Planned impairment
Impairment scheduled in advance, such as a control unit replacement; coordinated and mitigated before it starts.
Plenum
Space used for environmental air, such as above a return-air ceiling; requires plenum-rated cable or metal raceway.
Point-to-point diagram
Wiring drawing showing each conductor from terminal to terminal.
Positive alarm sequence
Automatic sequence that results in an alarm even though it may be delayed for investigation, unless reset.
Positive alarm sequence (PAS)
Automatic sequence that results in an alarm even though it is delayed for investigation, unless the system is reset (15 s + 180 s).
Power (P)
Energy per unit of time, in watts: P = E × I = I² × R = E² ÷ R.
Power-limited fire alarm (PLFA) circuit
Circuit powered by a source that complies with 760.121; installed per Parts I and III of Article 760.
Pre-alarm signal
Signal that results from detecting a pre-alarm condition; it must be distinctive from other signals (§10.10.8).
Pre-signal
Feature where initial signals sound only at a constantly attended location until a general alarm is started.
Pre-signal feature
Initial signal only at attended locations; the general alarm requires human action.
Pre-test
The contractor's own complete test of the system, with corrections, before the AHJ-witnessed acceptance test.
Presignal feature
A delay between the first alarm signal and general evacuation; allowed only when the AHJ and fire department approve (Section 907.5.1).
Presumed asbestos-containing material
Thermal system insulation and sprayed or troweled surfacing in buildings built no later than 1980, treated as asbestos until a survey shows otherwise (OSHA 1926.1101).
Presumed asbestos-containing material (PACM)
Thermal system insulation and surfacing material in buildings constructed in 1980 or earlier.
Private mode
Signaling only to the persons directing the emergency response (for example, a nurses' station); requires 10 dB above the average ambient.
Private operating mode
Audible and visible signaling only to persons directly concerned with emergency action.
Projected beam smoke detector
Detects smoke by obscuration of a light beam between a transmitter and a receiver or reflector.
Projected beam-type detector
A line-type smoke detector that measures the reduction (obscuration) of a light beam between a transmitter and a receiver or reflector.
Projected-beam detector
Smoke detector that senses obscuration of a light beam across a space; needs stable mounting surfaces.
Proprietary supervising station
A supervising station owned and staffed by the same owner as the protected properties.
Public mode
Audible or visual signaling to the general occupants of an area; requires 15 dB above the average ambient.
Pull point
Box or conduit body where conductors can be pulled; no more than 360 degrees of bends are allowed between pull points.
Punch list
A list of items to correct or finish before final acceptance.
Qualified
A competent and capable person or company that meets the requirements and training for a given field, acceptable to the AHJ.
Qualified person
Person with the skills, knowledge, and safety training to install and operate the equipment; only such persons may access the fire alarm disconnect.
Qualified personnel
Persons who meet the evidence of qualification in Section 10.5; installers must be qualified or supervised by qualified persons.
Quality assurance / quality control
QA is the planned system that prevents defects; QC is the inspection and testing that detects them.
Quiescent load
Current the system draws in its normal condition, without alarm.
Raceway
Enclosed channel designed to hold conductors or cables, such as EMT, RMC, or rigid PVC conduit.
Radiant energy-sensing fire detector
A detector that responds to radiation (ultraviolet or infrared) from a flame or spark; requires line of sight.
Rate-compensated detector
Heat detector that operates when the surrounding air reaches its set point, regardless of how fast the temperature rises.
Rate-compensation detector
Responds when the surrounding air reaches a preset level regardless of the rate of rise, compensating for thermal lag.
Rate-of-rise detector
Responds when the temperature rises faster than a preset rate, typically about 15°F per minute.
Reacceptance test
Testing required after an addition or change to the system, scaled to what was changed (§14.4.2).
Reacceptance testing
Testing after components, wiring, or software are added, deleted, repaired, or modified (14.4.2).
Recall program
Manufacturer program to correct or replace defective equipment; the owner must be told in writing.
Record (as-built) drawings
Shop drawings updated to reflect the actual installation of the system (§7.5.5).
Record drawings
Drawings that document device and appliance locations, wiring sequences and methods, and system connections as installed (as-builts).
Record drawings (as-builts)
Shop drawings updated to show the actual installation, delivered with the sequence of operation as programmed (NFPA 72 §7.5.5).
Record of completion
Document for the completed installation (Fig. 7.8.2(a)); revised after software changes.
Record of inspection and testing
Form in Fig. 7.8.2(g) and its supplements, or an equivalent alternative record, used to document periodic ITM.
Recordable case
Work-related injury or illness meeting the OSHA 1904 criteria, such as medical treatment beyond first aid, days away, or restricted work.
Redline
Field markup of the drawings that records the actual installation; the working source of the record drawings.
Redlines
A working copy of the drawings on which field changes are marked in red; used to prepare the record drawings.
Redundant path
Second path that maintains communication if the first one fails (Classes A, N, X).
Referenced standard
Document that a code adopts by reference, at the edition named in the code (for example NFPA 72 in IBC Chapter 35).
Reflected ceiling plan
A plan of the ceiling as seen from below, showing grid, lights, diffusers, and beams.
Reflected ceiling plan (RCP)
A ceiling plan drawn as if reflected onto the floor; shows lights, diffusers, ceiling heights, and beams.
Regulated power supply
Supply that holds its output voltage constant over its rated load and input range.
Releasing service
FACU that actuates a suppression system (clean agent, preaction, etc.).
Remote access
Connection to a control unit from a remote device for testing, diagnostics, or software updates, with time-out and on-site personnel rules.
Request for information (RFI)
A formal written question to the designer to clarify conflicts or omissions in the documents.
Resistance (R)
Opposition to current flow, measured in ohms (Ω) with the circuit de-energized.
Resource leveling
Shifting work, usually within float, so that resource demand does not exceed availability; it can extend the finish date.
Retainage
Percentage withheld from progress payments until the work is complete.
Retard
A waterflow switch setting that prevents alarms from pressure surges; total activation must still occur within 90 s.
Retard (waterflow)
Delay built into a waterflow switch to ride out pressure surges; the alarm must still be initiated within 90 seconds of the flow.
Retroactivity
Application of a code edition to installations that existed or were approved before its effective date; generally not required.
Reverse polarity supervision
A method in which the NAC is supervised in standby with reversed polarity (the appliance diodes block current) and the polarity is reversed in alarm to energize the appliances.
Revision cloud
A cloud-shaped outline drawn around a changed area, tied to a revision number in the revision block.
Revision cloud and delta
Cloud around a change plus a numbered triangle that ties it to the revision block.
RFI
Request for information: a written question to the designer about a conflict, omission, or unclear item.
RFI (request for information)
A formal written question to the designer to resolve a conflict, omission, or unclear requirement.
Ring-back
Control unit feature that signals again when a trouble-silence switch is left in the silenced position.
Riser
Vertical cable run penetrating more than one floor or in a vertical shaft; requires riser-type cable (FPLR) or better.
Riser diagram
A building cross-section showing circuits, devices per floor, and number of conductors (§7.4.6).
Root cause
The underlying reason an event keeps recurring; corrected instead of masking symptoms.
Round-trip resistance
Resistance of the outgoing plus return conductors, used to calculate voltage drop.
Safety Data Sheet (SDS)
16-section document with a chemical's hazards, PPE, and first aid.
Secondary power supply
Batteries (or another approved source) that keep the system operating when primary power fails.
Sensitivity test
A calibrated measurement that verifies a smoke detector is within its listed and marked sensitivity range.
Sensitivity testing
Verification with a calibrated method that a smoke detector is within its listed and marked range.
Separated occupancies
Mixed uses divided by fire barriers and horizontal assemblies per Table 508.4 (Section 508.4).
Separated occupancy
Occupancies divided by fire-resistance-rated barriers so each part is evaluated under its own requirements.
Sequence of operation
A description, in matrix or narrative form, of what the system does for each signal (§7.2.1(4), §7.4.9).
Series circuit
A single current path; resistances add and the current is the same throughout the loop.
Service provider
The company or person performing service, testing, or repair; reports to the AHJ when a system is out of service more than 8 hours.
Shaft enclosure
A rated enclosure for openings through floors, such as elevator hoistways and riser shafts (Section 713).
Shall / Should
'Shall' indicates a mandatory requirement; 'should' indicates a recommendation that is not required.
Shop drawings
The contractor's installation drawings with device locations, riser, diagrams, and calculations; the basis for the record drawings (NFPA 72 §7.4).
Short circuit
Low-resistance connection between conductors that bypasses the load or the EOL.
Short-circuit isolator
Device that opens a shorted section of an SLC so the rest of the loop keeps operating.
Shunt trip
Automatic disconnection of elevator main-line power before sprinkler discharge (§21.4).
Side rail
Either of the two long side members of a ladder.
Signal word
"Danger" (more severe hazard) or "Warning" (less severe) on a GHS label.
Signaling line circuit (SLC)
Pathway between addressable devices, interfaces, control units, or transmitters that carries multiple input and/or output signals.
Silent testing
Proving every input at the control unit without sounding the appliances, then operating the appliances and interfaces once at the end (annex to 14.4.3).
Simulated operation
A test in which a device, circuit, function, or interface is made to look operated without actually operating it; the test form must say so (14.6.4).
Single-action manual box
A manual fire alarm box that sends an alarm with one motion, such as pulling the handle.
Site-specific software
Programming unique to the installation (input/output mapping, labels, control matrix).
Sleeping area
A space intended or reasonably used for sleeping (hotel room, room with a sofa bed, on-call room); requires 75 dBA, 520 Hz, and 110 or 177 cd visual appliances.
Smoke barrier
A continuous membrane that resists the passage of smoke (Section 709); penetrations are rated for air leakage (L rating).
Smooth ceiling
A ceiling without continuous projections (beams, joists) that obstruct the flow of smoke or heat beyond what NFPA 72 allows.
Solid joist
Closely spaced projection (more than 4 in. deep, 36 in. or less on center) that restricts heat flow; heat spacing is halved across it.
Solid joist construction
A ceiling with solid members projecting down at close intervals; reduces heat detector spacing to 50 percent at right angles to the joists.
Spacing (S)
The listed or nominal distance between detectors on a smooth ceiling: 30 ft nominal for smoke detectors, the listed value for heat detectors.
Special inspection
Inspection and testing by a qualified independent inspector required by the building code, such as the acceptance testing of a smoke control system.
Spot-type detector
A detector whose sensing element is concentrated at one point, like most ceiling smoke and heat detectors.
Squib
Explosive-type actuator on some suppression releasing circuits; tested with an approved flashbulb or test light.
Standby (quiescent) load
Current the system draws in its normal, non-alarm condition; it is carried for 24 hours in the battery calculation.
STI / CIS
Speech Transmission Index and Common Intelligibility Scale: numeric measures of voice intelligibility.
Stranded conductor
Conductor made of several strands; for the same AWG it has slightly more resistance than solid wire.
Stratification
When smoke stops rising because it has cooled to the temperature of the surrounding air, so it does not reach the ceiling.
Stray voltage
Unwanted voltage on installation conductors; NFPA 72 limits it to 1 V ac/dc in acceptance testing.
Submittal
A package of data sheets, shop drawings, and calculations sent for review before installation.
Substantial Completion
Stage at which the owner can occupy or use the work for its intended use; the architect certifies the date.
Supervised notification appliance control circuit
An output circuit that activates notification appliance circuits on control equipment (for example a power extender); monitored for integrity, trouble on a fault, one notification zone.
Supervised sprinkler system
System whose valves, tanks, and other conditions are monitored so an impairment produces a distinctive supervisory signal.
Supervising station
Facility that receives alarm, supervisory, and trouble signals; it must be notified before and after testing.
Supervisory current
Small current that flows through the EOL in standby; if it moves outside its window, the panel indicates trouble.
Supervisory signal
Signal for an abnormal condition in the supervision of other systems, processes, or equipment (for example, a closed valve).
Survivability level
NFPA 72 designation (0 to 4) of how well a pathway is protected from fire; independent of the pathway class.
Sync module
A listed device that sends the manufacturer's synchronization protocol to the appliances on one or more NACs.
Synchronization
Visual appliances flashing at the same time; required when more than two are in the same field of view.
T rating
Time a firestop system limits temperature rise on the unexposed side of the penetrating item to 325 °F above ambient.
T-tap
A branch taken from the middle of a circuit; on Class B IDCs and NACs it leaves sections unsupervised.
Tactile notification appliance
An appliance that alerts by touch (for example, a bed shaker); its performance is evaluated per UL 1971.
Take-off
Counting and measuring quantities of material and labor from the drawings.
Tamper switch
Supervisory switch on a normally open valve that signals when the valve leaves its open position.
Technical data sheet (cut sheet)
The manufacturer's document listing current draw, voltages, candela, listing, and compatibility of the equipment.
Temporal-3 (T3) pattern
The standard evacuation signal per ANSI/ASA S3.41: 0.5 s on / 0.5 s off three times, then 1.5 s off.
Temporal-4 (T4) pattern
The CO signal: four cycles of 100 ms on / 100 ms off, then 5 s off.
Test plan
Written document that clearly establishes the scope of the testing (14.2.10).
Testing
Operating a device or system to prove that it works, using the method in Table 14.4.3.2.
Textual visual notification appliance
An appliance that displays alphanumeric or pictorial messages, such as a message sign.
Through penetration
Opening that passes completely through a fire-resistance-rated wall or floor assembly.
Through-penetration firestop system
A listed, tested assembly that restores the rating of a wall or floor where cables, pipes or conduits pass through it.
Time-weighted average (TWA)
Average exposure over the work shift, usually 8 hours.
Toeboard
Low barrier (≥ 3.5 in.) at the platform edge that keeps objects from falling.
Top cap
The top of a stepladder; never used as a step.
Total float
Time an activity can slip without delaying the project finish (LS − ES).
Tourniquet
Band tightened 2–3 in. above a limb wound to stop life-threatening bleeding.
Trouble signal
Signal for an abnormal condition of the system due to a fault (open, ground, loss of power).
Type 2 sound level meter
An instrument meeting ANSI/ASA S1.4 Type 2, required to measure sound pressure levels during acceptance testing (A-weighting, FAST).
UL 864 / UUKL
UL 864 covers fire alarm control units; UUKL is the added listing category for smoke control system equipment.
Unit price contract
Payment per unit installed (device, foot) times the measured quantity.
Unregulated power supply
Supply whose output voltage follows the ac line voltage and the load.
Unwanted alarm
Alarm that does not result from a potentially hazardous condition. Subtypes: malicious, nuisance, unintentional, and unknown.
Valve supervisory switch (tamper switch)
A device that sends a supervisory signal when a sprinkler control valve moves from its normal position.
Valve-regulated lead-acid (VRLA) battery
Sealed battery typical of fire alarm panels; tested semiannually and replaced or load tested every 3 years.
Verification (§7.5.8)
Confirmation that functions operate per the approved plans and sequence, that documentation is complete and archived on site, and that corrective actions are confirmed in writing.
Visual notification appliance (strobe)
An appliance that alerts by sight; NFPA 72-2022 calls it 'visual' (formerly 'visible').
Visual warning signal ('fire hat')
Indicator in the elevator car that flashes when a hoistway or machine room detector operates.
Voltage (E)
Electrical potential difference, measured in volts (V) with the voltmeter in parallel.
Voltage drop
Voltage lost in the circuit conductors: current times conductor resistance.
Voltage drop (VD)
Voltage lost in conductor resistance: VD = I × R of the complete loop.
Volume allowance
Cubic inches that Table 314.16(B) assigns to each conductor, clamp, or device when calculating box fill.
VRLA battery
Valve-regulated lead-acid battery, the sealed type used as standby power; it has its own semiannual tests and a 3-year replace-or-load-test rule.
Waterflow switch
An alarm-initiating device that detects water flowing in a sprinkler system (vane or pressure type).
Wireway
Sheet-metal trough with a hinged or removable cover used to house and protect conductors; the conductors may fill no more than 20 percent of its interior area.
Working space
Clear space in front of equipment examined or serviced while energized (110.26): 3 ft deep at 0–150 V.
Written narrative
Text describing the intent and general operation of the system (§7.2.1(1)).
Zone
Defined area of the protected premises from which a signal is received, to which a signal is sent, or in which a form of control is exercised.