Managing Periodic Testing and Records (NFPA 72-2022 Ch. 14 and Ch. 7)

NFPA 72-2022 Ch. 14 · NFPA 72-2022 Ch. 7 · NFPA 72-2022 Section 10.21 · NFPA 72-2022 §10.5.3 · NFPA 72-2022 §23.8.2.11 · NFPA 72-2022 §26.6.2.3 · NFPA 101-2021 §9.6.1 · Outline tasks 3.2.1, 3.2.3

What NICET expects at Level III

Tasks 3.2.1 (manage periodic testing) and 3.2.3 (prepare documentation and records) belong to the Maintenance domain, 25 to 35 percent of the Level III exam. At Level II you carry out a test and fill in the form. At Level III you decide what the program must contain, schedule it so every component is tested on or before its own due date, assign people who are allowed to do the work, coordinate with the owner, the supervising station, and other trades, and then review the paperwork the way an AHJ auditor would. Expect scenarios: Which plan complies? What is missing from this record? When is the next test due? Correcting impairments and deficiencies is task 3.2.2 and commissioning is 3.1.3, so this pack stays on the program and the records.

1. The two tables set the frequencies

FrequencyTypical items
WeeklyVisual inspection of an unmonitored control unit (Table 14.3.1)
QuarterlyVisual inspection of flame and video image detectors (Table 14.3.1)
SemiannualWaterflow and control valve supervisory switch tests, flame detector tests, and VRLA battery temperature, charger, voltage, and ohmic tests (Table 14.4.3.2); visual inspection of manual boxes, smoke and heat detectors, and notification appliances (Table 14.3.1)
AnnualMost functional tests: control unit, smoke detectors, manual boxes, notification appliances, supervising station transmitters (Table 14.4.3.2)

Measure each interval from the component's own last test. The tables give only the frequency (Weekly, Quarterly, Semiannually, Annually) and state no grace period, so do not assume one: schedule each component on or before its due date, and use a tolerance only where the AHJ or the contract states it. A test split over several visits leaves every device on its own due date, and a device that was skipped stays overdue until it is actually tested. Testing and inspection follow the AHJ's schedule or the Table 14.4.3.2 and Table 14.3.1 frequency, whichever is more frequent (§14.3.1, §14.4.4). The 2022 edition has no Table 14.4.5; frequencies are in the Periodic Frequency column of the two tables.

2. What goes on the calendar

ComponentVisual (Table 14.3.1)Test (Table 14.4.3.2)
Monitored control unitAnnual (trouble signals semiannual)Annual
Unmonitored control unitWeeklyAnnual
Manual boxes, smoke, heat, duct detectorsSemiannual (duct sampling tube annual)Annual
Flame and video image detectorsQuarterlyFlame: semiannual
Waterflow and valve supervisory devicesSemiannualSemiannual
Notification appliances, ECF interfacesSemiannualAnnual
Remote annunciators, surge protective devicesSemiannualAnnunciators: annual
NAC power extenders, remote power supplies, fiber connectionsAnnualTested through the circuits and power supplies they serve
Supervising station transmittersAnnualAnnual
VRLA batteriesMarking semiannualSemiannual tests; replace or load test every 3 years

3. Test plan, notification, and crew

4. Reacceptance and software

ChangeRequiredSection
Device, appliance, or relay addedFunctionally test it14.4.2.1
Device, appliance, or relay deletedOperate another one on the circuit14.4.2.2
Control unit hardware modified or repairedTest the control unit per Table 14.4.3.214.4.2.3
Site-specific software100% of affected functions + 10% of unaffected initiating devices (max. 50) + revised record of completion14.4.2.4
Executive software (firmware)10% functional test with a device on each input and output circuit14.4.2.5
Changed from off siteQualified person at the premises14.4.2.6

5. Batteries and sensitivity

VRLA batteries get semiannual temperature, charger, cell/unit voltage, and ohmic tests (a baseline ohmic value is recorded at installation; replace at a 30% conductance or 40% resistance deviation) and a replacement or load test every 3 years; passing the semiannual tests does not waive it. Replace at 80% capacity or less, or at the next scheduled test if below 85%. Smoke detector sensitivity is checked within 1 year of installation and then in alternate years; after the second in-range test it may be extended to a maximum of 5 years, measured from that last test (§14.4.4.3). System smoke detector functional tests are annual for every detector and are not rotated. Before any battery testing that disconnects power, make sure the software held in volatile memory is protected from loss (Table 14.4.3.2).

6. Records and reports

RecordKeepSection
Permanent: reproducible as-builts, O&M manuals, written sequence of operation, site-specific software documentationLife of the system, owner responsible, for any AHJ; paper or electronic14.6.1
ITM recordsUntil the next test + 1 year, on a medium that survives that period; paper or electronic14.6.2.1, 14.6.2.3
Impairment recordsKept by the owner or designated representative for 1 year from the date the impairment is corrected10.21.2
Supervising station test signalsAt least 12 months; hard copy to the AHJ on request14.6.3
Revised record of completionSupplements the original unaltered documents and carries a revision date7.5.6.6
Test plan and resultsWith the testing record14.2.10
Inspection and test recordFigure 7.8.2(g) with supplements (h) to (l), or an alternative with the same information7.6.6

Common traps: the tables give no grace period, so a device missed during a split test stays overdue on its original date; the 8-hour report is NFPA 72 and the 4-hour fire watch is NFPA 101; smoke detector functional tests cannot be rotated even though sensitivity can reach 5 years; the AHJ may demand more than the table; and the test plan is a record, not a throwaway planning sheet.

Finding it in your printed books: tab Chapter 14 at 14.2 (14.2.3, 14.2.4, 14.2.6, 14.2.10), Table 14.3.1, 14.4.2, 14.4.4, Table 14.4.3.2 (items 4, 8, 9, 17, 18, 24), and 14.6. In Chapter 7 tab 7.5.6, 7.5.7, 7.6.6, 7.7, and the 7.8.2 forms. Also tab Section 10.21, and §23.8.2.11 and §26.6.2.3 for remote work. Look up in the index: Inspection, Testing, Records, Test plan, Reacceptance testing, Impairments, Remote access, Site-specific software. An asterisk next to a section number means Annex A text exists. In NFPA 101, tab §9.6.1.

What to tab in your books

SectionWhy
NFPA 72 §14.2.3Owner responsibility; delegation by lease or agreement; ITM by others under a written contract
NFPA 72 §14.2.5Record of completion and Chapter 7 information provided to service personnel on request
NFPA 72 §14.2.4Notification before testing and when testing is complete
NFPA 72 §14.2.6Releasing service: qualified testers, occupant notification, securing the suppression system
NFPA 72 §14.2.10Test plan: scope, documented with the testing record
NFPA 72 §14.4.4 and §14.3.1Frequency rule: the AHJ's schedule or the table frequency, whichever is more frequent
NFPA 72 Table 14.3.1Visual inspection frequencies by component
NFPA 72 Table 14.4.3.2Test frequencies and methods (items 4, 8, 9, 17, 18, 24)
NFPA 72 §14.4.2Reacceptance testing: added or deleted devices, control unit hardware, software changes
NFPA 72 §14.4.4Testing frequency: 18-month limit for inaccessible devices (14.4.4.1), sensitivity (14.4.4.3), interfaced equipment (14.4.4.4)
NFPA 72 §10.5.3Qualified personnel for inspection, testing, and service
NFPA 72 Section 10.21Impairments: owner notice, AHJ report after 8 hours, mitigation, notice when the impairment ends, 1-year record
NFPA 72 §23.8.2.11Remote access for testing, diagnostics, and software updates
NFPA 72 §26.6.2.3Remote programming of transmitting technologies
NFPA 72 §14.6Records: permanent (14.6.1), ITM (14.6.2), supervising station (14.6.3)
NFPA 72 §7.5.6 and §7.5.7Record of completion (revisions, lost originals, electronic filing) and site-specific software documentation
NFPA 72 §7.6.6, §7.7, §7.8.2ITM record, record availability and archiving, documentation cabinet, and forms (g) through (l)
NFPA 101-2021 §9.6.1Required fire alarm out of service more than 4 hours in 24
NFPA 72 Figure A.14.6.1.1Typical input/output matrix (sequence of operation)

Chapter vocabulary

Periodic frequency
The interval in the Periodic Frequency column of Table 14.3.1 and Table 14.4.3.2 (for example weekly, quarterly, semiannual, annual); the AHJ may require more frequent inspection or testing.
Inspection
A visual check of location, condition, and obstruction, done at the Table 14.3.1 frequencies.
Testing
A functional check of operation, done by the methods and frequencies of Table 14.4.3.2.
Test plan
The written document that establishes the scope of testing and is kept with the test results.
Reacceptance testing
Testing after a change to the system, scaled to what was changed (Section 14.4.2).
Impairment
A condition in which a system or part of it is not functional, including planned out-of-service events.
Deficiency
A condition that does not meet code or design intent and must be corrected; if uncorrected at the end of ITM, the owner is told in writing within 24 hours.
Observation
A suggested correction or enhancement that is not an impairment or deficiency, such as an optional software update.
Permanent records
Reproducible as-built drawings, O&M manuals, written sequence of operation, and software documentation, kept for the life of the system.
Record drawings
Shop drawings updated to show the system as actually installed.
Record of completion
The form (Figure 7.8.2(a)) completed by the installer at acceptance and revised when the system is modified.
Site-specific software
Program that defines the inputs, outputs, labels, and operation of one installation.
Executive software
The control unit's operating program, also called firmware.
VRLA battery
Valve-regulated lead-acid battery, the sealed type used as standby power; it has its own semiannual tests and a 3-year replace-or-load-test rule.
Ohmic test
Measurement of a cell's conductance, resistance, or impedance, compared with the baseline recorded at installation.
Sensitivity test
Check that a smoke detector is within its listed and marked sensitivity range, done within 1 year and then in alternate years.
ECF interface device
The fire alarm system component that connects to an emergency control function, such as the relay that recalls an elevator.
Releasing service
Use of a fire alarm control unit to release a suppression system, which brings extra rules for testers and notification.
Mitigation plan
Plan naming who contacts the communications center if a real alarm occurs during remote programming of transmitters.
Remote access
Connection to a control unit from a remote device for testing, diagnostics, or software updates, with time-out and on-site personnel rules.
Documentation cabinet
The cabinet labeled SYSTEM RECORD DOCUMENTS where record documents are kept; none are stored inside the control unit.
Designated representative
The person the owner names to carry out the owner's inspection, testing, and maintenance responsibilities.

40 practice questions cover this chapter, each with an explanation and the code section. Get lifetime access or try the free practice exam.