Shop Drawings and Submittals (NFPA 72 Ch. 7, 10, 12, 17, 18, 21)

NFPA 72-2022 Ch. 7 · NFPA 72-2022 §1.5 · NFPA 72-2022 §10.3–10.6, §10.17 · NFPA 72-2022 Ch. 12, 17, 18, 21 · IBC-2021 §107 and §907.1 · NFPA 70-2020 §760 and §300.11 · Outline tasks 3.3.1

What NICET expects at Level III (task 3.3.1)

Domain 3.3, Submittal Preparation and System Layout, is worth 20 to 30 percent of the Level III exam and has one task: 3.3.1 Prepare and approve shop drawings. A Level III technician works independently, reads NFPA 72, the NEC, the IBC, and NFPA 101 together with the specifications, produces the submittal packet, and reviews other people's drawings before they go to the AHJ. Expect a small exhibit described in words (a schedule, a plan, a matrix row, a calculation sheet) and a question that asks you to spot the error, choose the compliant design, or decide what to send back. The answer is rarely one look-up: it is a look-up plus a judgment about who must approve what, and what you must not do on your own.

What a complete submittal contains

DocumentWhat the reviewer checksSource
Minimum documentation listWritten narrative, riser diagram, floor plans, sequence of operation, equipment data sheets, manufacturers' published instructions, battery capacity and de-rating calculations, NAC voltage drop calculations, mounting heights of wall-mounted devices, minimum sound pressure levels, pathway diagrams to the supervising stationNFPA 72 §7.2.1
General information, sequencePremises, owner, installer, symbols, date of issue and revision dates on every sheet (§7.4.4). Sequence of operation as an input/output matrix or a narrative (§7.4.9).§7.4.4, §7.4.9
Floor plansNorth arrow, graphic scale, walls and doors, partitions within the top 15 percent of ceiling height, room use, devices, primary power disconnect, devices and conductors per circuit, ceilings over 10 ft and beams, pathway class and survivability level with EOL locations§7.4.5
Riser diagramCross-section arrangement, number of risers, circuits per riser, devices per circuit per floor, number of conductors per circuit§7.4.6
Control unit diagram, typical wiringControl unit diagram: equipment and location, field wiring terminals and identification, circuits connected, indicators and controls. Typical wiring: initiating devices, notification appliances, remote indicators, annunciators, remote test stations, EOL and power supervisory devices.§7.4.7, §7.4.8
CalculationsBattery capacity with correction factor; NAC voltage drop; other (for example line resistance)§7.4.10, §10.6.7.2
Shop drawing rulePrepared in accordance with NFPA 72 and submitted for review and approval before installation. The IBC points to NFPA 72 for the content.IBC §907.1.2

Reviewing the design: numbers to check

ItemCheckSource
Smoke detector spacing, smooth ceiling30 ft nominal with half-spacing to walls, or every point within 0.7S (21 ft). Partitions within the top 15 percent of the ceiling height act as walls. Spacing beyond this needs a documented performance-based design accepted by the AHJ.§17.7.4.2.3
Smoke detectors and beamsBeams shallower than 0.1H: smooth-ceiling spacing. Beams at least 0.1H deep and at least 0.4H apart: a detector in each pocket. Beams at least 0.1H deep but closer than 0.4H: spacing at right angles to the beams is cut to half.§17.7.4.2.4
Heat detectors above 10 ftMultiply the listed spacing: 10-12 ft 0.91, 12-14 0.84, 14-16 0.77, 16-18 0.71, 18-20 0.64, 20-22 0.58, 22-24 0.52, 24-26 0.46, 26-28 0.40, 28-30 0.34. The table stops at 30 ft.Table 17.6.3.5.1
Control unitHighest switch, lamp, or display 6 ft maximum; lowest 15 in. minimum. Smoke detection at the control unit, NAC power extenders, and transmitters where not continuously occupied (2022 lets the AHJ accept a risk analysis instead).§10.4.4, §10.4.5
Audible, public and sleeping modesPublic: greater of 15 dB over average ambient or 5 dB over the maximum lasting 60 s or more, at 5 ft; 110 dBA ceiling. Sleeping rooms: the greatest of those two or 75 dBA at the pillow, with a 520 Hz signal from listed equipment.§18.4.4.1, §18.4.6
Visible, wall-mountedEntire lens 80-96 in. Candela by room size: 20x20 15; 28x28 30; 30x30 34; 40x40 60; 45x45 75; 50x50 94. Not centered or not square: greater of the farthest wall or twice the farthest adjacent wall.§18.5.5.1, Table 18.5.5.7.1(a)
Visible, otherCeiling above 30 ft: suspend at or below 30 ft or go to wall mounting. Corridors up to 20 ft wide: 15 cd, 15 ft from the ends, 100 ft apart. Sleeping: 177 cd if the lens is within 24 in. of the ceiling, else 110 cd. Consider obstructions, including the direct view of corridor appliances.§18.5.5.6-§18.5.5.10
PathwaysClass A and X need a true return path (no branches or spurs) and separated outgoing and return routes. Level 1 = sprinklered building plus metal raceway; Level 2 = 2-hour protection; Level 3 = both; Level 4 = 1-hour.§12.3, §12.4

Calculations that get approved or rejected

Conflicts, deviations, and approvals

Other 2022 items a reviewer should catch

Common traps:
Finding it in your printed books:

What to tab in your books

SectionWhy
NFPA 72 §1.5Equivalency: technical documentation to the AHJ, AHJ approval
NFPA 72 §7.2.1Minimum required documentation, including mounting heights and sound pressure levels
NFPA 72 §7.3Design documents: pathway class and survivability designations
NFPA 72 §7.4.4–7.4.5General information, date of issue and revisions; floor plan contents
NFPA 72 §7.4.6–7.4.8Riser diagram, control unit diagram, and typical wiring contents
NFPA 72 §7.4.9–7.4.10Sequence of operation and required calculations
NFPA 72 §10.3Equipment listed for the purpose and compatible with the control unit
NFPA 72 §10.4.4–10.4.7Control unit heights; smoke detection at control equipment; abandoned equipment
NFPA 72 §10.5Personnel qualifications, including system designers
NFPA 72 §10.6.7.2Secondary power: 24 h + 5 min (15 min voice); 1.25 correction factor
NFPA 72 §10.17Notification appliance circuits and supervised control circuits
NFPA 72 §12.3 and §12.4Pathway classes and survivability levels
NFPA 72 Table 17.6.3.5.1Heat detector spacing reduction by ceiling height
NFPA 72 §17.7.4.2.3–17.7.4.2.4Smoke detector spacing, 0.7S, and beams; §17.7.4.6 for air sampling
NFPA 72 §18.4.4.1 and §18.4.6Public-mode and sleeping-area audibility (Annex D covers intelligibility)
NFPA 72 Table 18.5.5.7.1(a)/(b)Room spacing candela; §18.5.5.6–18.5.5.10 for obstructions, corridors, sleeping
NFPA 72 §21.3–21.4, §21.8, §23.8.5.1.3Elevator recall and shutdown, hoistway devices, HVLS fan interlock, dedicated-function systems
IBC §107.3.4.1 and §107.4Deferred submittals; amended construction documents
IBC §907.1.2Fire alarm shop drawings: prepared per NFPA 72, approved before installation
NFPA 70 §760.24, 760.25, 760.41(B), 300.11Cable support, abandoned cable, dedicated branch circuit without GFCI or AFCI

Chapter vocabulary

Shop drawings
Installation drawings prepared by the contractor, showing devices, wiring, and equipment in the form NFPA 72 Section 7.4 requires, submitted before installation.
Submittal
The package sent for review: shop drawings, data sheets, calculations, and related documents.
Record drawings
Shop drawings updated to show what was actually installed (as-builts).
RFI (request for information)
A formal written question to the designer to resolve a conflict, omission, or unclear requirement.
Deferred submittal
A portion of the design not submitted with the permit application, to be submitted later through the design professional and approved before installation.
Amended construction documents
Revised documents submitted for approval when changes during construction depart from the approved set.
Equivalency
Use of a system, method, or device of equivalent or superior effectiveness, shown by technical documentation and approved by the AHJ (§1.5).
Performance-based design
A design justified by goals, criteria, and analysis rather than by prescriptive spacing or layout rules; accepted by the AHJ.
Sequence of operation
Description of what each input causes the system to do, as a narrative or an input/output matrix.
Input/output matrix
A table that lists each initiating input and marks every output it must trigger.
Pathway class
Designation (A, B, C, D, E, N, X) describing how a circuit is arranged and how its faults are tolerated.
Pathway survivability level
Designation (0 to 4) describing protection of a pathway against fire damage, such as sprinklers with metal raceway or 2-hour cable.
Acoustically distinguishable space (ADS)
A zone or subdivision with its own acoustic, environmental, or use characteristics, used to plan voice intelligibility.
Effective intensity (candela)
The light output rating of a visible notification appliance used in the room spacing tables.
Correction factor (battery)
The 1.25 multiplier NFPA 72-2022 applies to the calculated amp-hours (the earlier editions used a 20 percent margin).
Voltage drop
The loss in voltage along circuit conductors, equal to current times conductor resistance.
Listed compatible
Evaluated by a testing laboratory for use with a specific control unit, not merely listed on its own.
Reflected ceiling plan (RCP)
A plan that shows the ceiling as if reflected onto the floor: lights, diffusers, soffits, heights, and beams.
Revision cloud
A cloud-shaped outline drawn around a changed area, tied to a revision number in the revision block.
Approved as Noted
A review action that lets work proceed with the reviewer's corrections; Revise and Resubmit does not.
Authority having jurisdiction (AHJ)
The organization or individual that enforces the code and approves plans, equipment, and installations.
Abandoned equipment
Fire alarm equipment no longer in use. NFPA 72-2022 requires it to be removed and to be marked "not in service" until it is removed.
Supervised notification appliance control circuit
An output circuit that activates notification appliance circuits on control equipment (for example a power extender); monitored for integrity, trouble on a fault, one notification zone.

32 practice questions cover this chapter, each with an explanation and the code section. Get lifetime access or try the free practice exam.