PassFAS

Key numbers (NFPA 72 · NEC · OSHA)

Quick reference

The values asked most often, with their section in the exam editions (NFPA 72-2022, NEC 2020, current OSHA). Where the exact subsection could not be confirmed, the general section is cited. The 2022 edition renumbered parts of Chapters 17 and 18, so if your book is a different edition the numbers may not match.

Power and signals (NFPA 72 Ch. 10 and 12)

TopicValueSection
Secondary power (batteries)24 h standby + 5 min alarm; voice systems (EVACS): 24 h + 15 min§10.6.7.2
Battery capacity marginA safety margin is required in the calculation; industry sources report 25% in the 2022 edition (previously 20%)§10.6.7 / §7.2.1
Battery markingMonth and year of manufacture§10.6.10.1
Control unit branch circuitDedicated, red-marked disconnect, accessible only to authorized personnel, location identified at the control unit§10.6.5
Control unit display heightHighest control ≤ 6 ft; lowest ≥ 15 in. above the floor§10.4.4
Smoke detection at the control unitWhere the area is not continuously occupied§10.4.5
Notification start≤ 10 s after an initiating device activates§10.11.1
Trouble annunciation≤ 200 s after the fault§12.6.1
Silenced troubleResounds every ≤ 24 h until corrected§10.15
ImpairmentNotify the owner; if the system is out of service more than 8 h, the service provider notifies the AHJ. (The “4 hours” with a fire watch comes from NFPA 101/IFC.)§10.21
Uncorrected deficiencyReported to the owner in writing within 24 h§14.2.2

NEC 2020 (Article 760 and Chapter 9)

TopicValueSection
Branch circuit (NPLFA and PLFA)No GFCI or AFCI; red-identified disconnect marked “FIRE ALARM CIRCUIT”; accessible only to qualified personnel; location shown at the control unit760.41(B) · 760.121(B)
NPLFA overcurrent protection18 AWG: 7 A · 16 AWG: 10 A760.43
PLFA separation from light and power2 in. (50 mm) where neither is in a raceway760.136(G)
PLFA cablesFPLP plenum · FPLR riser · FPL general; a higher rating may substitute for a lower one760.154 · Table 760.154(A)
CI cable on steelSupported every 24 in.760.24(B)
Abandoned cablesRemove the accessible portion (unless tagged for future use)760.25
SupportFrom the building structure; not from ceiling grid or its support wires760.24(A) · 300.11
Conduit fill1 conductor 53% · 2 conductors 31% · over 2: 40%Ch. 9, Table 1

Initiating devices (NFPA 72 Ch. 17)

TopicValueSection
Smoke detector on a sidewallBetween the ceiling and 12 in. below it (to the top of the detector)§17.7.4.2
Smoke spacing, smooth ceiling30 ft nominal; every point within 0.7 × S (21 ft) of a detector§17.7.4.2.3.1
Smoke detector environment32–100 °F, humidity below 93%, air velocity below 300 ft/min (unless listed otherwise)§17.7.1
Detectors during constructionNot installed until cleanup is complete unless the AHJ requires it; if installed, protected§17.7.2
Spot heat detectorOn the ceiling ≥ 4 in. from the wall, or on the wall 4–12 in. below the ceiling§17.6.3.1.3
Heat detector ratingAt least 20 °F above the maximum expected ceiling temperature§17.6.2
Nonrestorable heat detectorsAt 15 years: replace, or lab-test 2 of every 100Table 14.4.3.2
Manual fire alarm boxOperable part 42–48 in. above the floor; ≤ 5 ft from each exit; travel ≤ 200 ft§17.15
WaterflowAlarm ≤ 90 s after flow equal to one sprinkler§17.13.2
Valve supervisory switchSignal within 2 revolutions of the handwheel or 1/5 of the travel§17.17.1

Notification (NFPA 72 Ch. 18)

TopicValueSection
Public mode15 dB above average ambient or 5 dB above the maximum lasting ≥ 60 s (whichever is greater), 5 ft above the floor§18.4.4.1
Private mode10 dB above average ambient or 5 dB above the 60 s maximum§18.4.5.1
Sleeping areasGreatest of 15 dB / 5 dB / 75 dBA at the pillow; 520 Hz low-frequency signal§18.4.6
Maximum110 dBA at the minimum hearing distance; average ambient above 105 dBA requires visible appliances§18.4.1
Wall-mounted audibleTop ≥ 90 in. above the floor and ≥ 6 in. below the ceiling§18.4.9.1
Wall-mounted visibleEntire lens between 80 and 96 in. above the floor§18.5.5.1
Flash rate1–2 Hz; clear or nominal white; ≤ 1000 cd§18.5.3
Candela table, wall-mounted20×20 → 15 cd · 28×28 → 30 · 30×30 → 34 · 40×40 → 60 · 45×45 → 75 · 50×50 → 94Table 18.5.5.7.1(a)
Corridors (≤ 20 ft wide)≥ 15 cd; ≤ 15 ft from each end; ≤ 100 ft apart§18.5.5.8
Sleeping rooms177 cd if the lens is less than 24 in. from the ceiling, otherwise 110 cd; within 16 ft of the pillow§18.5.5.10

Circuits, control functions and supervision (Ch. 12, 21, 23, 26)

TopicValueSection
Class A / X outgoing and returnRouted separately; allowed together for ≤ 10 ft where entering a device, for a single drop, or in areas ≤ 1000 ft². (1 ft vertical / 4 ft horizontal is only an annex recommendation.)§12.3.8.1
Pathway survivabilityLevels 0 to 4§12.4
Emergency control relayWithin 3 ft of the controlled component§21.2.4
Elevator power shutdownHeat detector within 2 ft of each sprinkler, rated lower than the sprinkler§21.4
Positive alarm sequenceAcknowledge within 15 s; investigate up to 180 s§23.8.1.2.1.1
Alarm verificationMaximum delay 60 s§23.8.5.4
DACTTwo means of transmission; each channel tested at least every 6 h; call attempt ≤ 90 s§26.6.4
Central stationRetransmit alarms immediately; runner within 2 h§26.2 · §26.3

Inspection, testing and records (Ch. 14 and 7)

TopicValueSection
Smoke detector sensitivityWithin 1 year of installation, then every other year; may be extended up to 5 years if stable§14.4.4.3
Software change100% of affected functions + 10% of unaffected initiating devices (max. 50)§14.4.2.4
ITM recordsUntil the next test and for 1 year after§14.6.2.1
Permanent recordsFor the life of the system§14.6.1.3
Stray voltage on conductors≤ 1 VTable 14.4.3.2
System documentsIn a documentation cabinet (not inside the control unit)§7.7.2
FormsRecord of completion: Figure 7.8.2(a) · Inspection and testing: Figure 7.8.2(g)§7.8.2

There is no Table 14.4.5 in the 2022 edition. Test frequencies are in the Periodic Frequency column of Table 14.4.3.2. A lot of older study material still cites a separate “Table 14.4.5, Testing Frequencies”.

ComponentVisual inspection (Table 14.3.1)Test (Table 14.4.3.2)
Monitored control unit (fuses, LEDs, primary power)Annual (trouble signals: semiannual)Annual
Unmonitored control unitWeeklyAnnual
Manual boxes, smoke, heat and duct detectorsSemiannualAnnual
Flame detectorsQuarterlySemiannual
Waterflow devicesSemiannual (was quarterly)Semiannual
Control valve supervisory (tamper) switchSemiannualSemiannual
Other supervisory: air pressure, temperature, water levelSemiannualAnnual
Notification appliancesSemiannualAnnual
VRLA batteriesSemiannual (includes the date of manufacture)Semiannual (temperature, charger, voltage, ohmic test); replace or load-test every 3 years
Secondary power—Annual (5 min in alarm; 15 min for voice systems)
Supervising station transmittersAnnualAnnual
Household smoke alarms—Replace at 10 years

Read each frequency from the Periodic Frequency column of Table 14.3.1 (inspection) or Table 14.4.3.2 (testing), and count the interval from the date of the last inspection or test: semiannual items come due about 6 months later and annual items about 12 months later.

Safety (OSHA and first aid — these books are not allowed in the test center)

TopicValueSection
Ladder to an upper landingSide rails ≥ 3 ft above the landing1926.1053(b)(1)
Ladder angleBase 1/4 of the working length from the wall (4:1)1926.1053(b)(5)(i)
StepladderDo not use the top or top step as a step1926.1053(b)(13)
Near energized equipmentLadders with nonconductive side rails1926.1053(b)(12)
Fall protectionConstruction 6 ft · general industry 4 ft · scaffolds 10 ft1926.501 · 1910.28 · 1926.451(g)
GuardrailTop rail 42 in. ± 3 in.; withstands 200 lb1926.502(b)
Personal fall arrestFree fall ≤ 6 ft; anchorage 5,000 lb per person1926.502(d)
ScaffoldsSupport 4 times the intended load1926.451(a)(1)
NoiseHearing conservation program from 85 dBA (8-h TWA); limit 90 dBA1910.95
TrenchesProtective system from 5 ft deep1926.652
Construction sitesGFCI on temporary receptacles (or an assured equipment grounding conductor program)1926.404(b)(1)
Safety data sheets (SDS)16 sections1910.1200(g)
Adult CPR100–120 compressions/min; at least 2 in. deep; 30 compressions : 2 breathsRed Cross

Practice for the real thing. Take the free 20-minute Level I practice exam (no account needed), or get lifetime access to 85-question exams in the NICET format and 552 Level I questions with explanations.