Your printed references are your only lookup tools on exam day, so how you tab them decides how fast you answer. NICET allows the books bound or in a three-ring binder, with highlighting and self-adhesive tabs that are permanently attached; handwritten notes, loose pages and repositionable tabs are not allowed. These are the sections worth a tab for Level I, chapter by chapter.

How to tab: one color per book, one tab per chapter on the side edge, and a second row on the top edge for the tables you use most. Label tabs with the section number and a keyword, e.g. “17.15 Pull stations”.

NFPA 72 (2022)

SectionWhyChapter
NFPA 72 §1.4.1Retroactivity: the code does not apply to existing installations unless stated or required by the AHJFundamentals
NFPA 72 §1.6Units: inch-pound with SI in parentheses; use one systemFundamentals
NFPA 72 §3.2Official definitions: Approved, AHJ, Labeled, Listed, Shall, ShouldFundamentals
NFPA 72 §3.3General definitions: signals, conditions, IDC/SLC/NAC, unwanted alarms, impairmentFundamentals
NFPA 72 §10.3Equipment listed for the purpose, compatibility, 85–110% voltage (§10.3.5)Fundamentals
NFPA 72 §10.4.4FACU display and control heights: 6 ft max. / 15 in. min.Fundamentals
NFPA 72 §10.4.5Smoke detection at FACUs, NAC extenders, and transmitters in areas not continuously occupiedFundamentals
NFPA 72 §10.5Qualifications of designers, installers, and ITM personnel (NICET in A.10.5.3.4(2))Fundamentals
NFPA 72 §10.6.5Primary supply: dedicated circuit, red marking, authorized access, breaker lockFundamentals
NFPA 72 §10.6.7Secondary supply: 24 h + 5 min (15 min for EVACS); 4 h batteries with an engine-driven generatorFundamentals
NFPA 72 §10.6.10Batteries: month/year marking, listed or recognized batteriesFundamentals
NFPA 72 §10.7Signal priority: alarm > supervisory > troubleFundamentals
NFPA 72 §10.10Distinctive signals (temporal-3 evacuation, supervisory, trouble, pre-alarm)Fundamentals
NFPA 72 §10.11.1Notification and control functions actuate within 10 sFundamentals
NFPA 72 §10.12Silencing of alarm notification and reactivationFundamentals
NFPA 72 §10.15Trouble signals: resound every 24 h or less (§10.15.9)Fundamentals
NFPA 72 §10.21Impairments: notifications, 1-year record, report to the AHJ after 8 hFundamentals
NFPA 72 §12.6.1Monitoring for integrity: open or ground indicated within 200 sFundamentals
NFPA 72 §23.8PAS (§23.8.1.2.1.1) and alarm verification (§23.8.5.4.1)Fundamentals
NFPA 72 §17.4General requirements: protection, independent support, accessibilityInitiating
NFPA 72 §17.6.2 / Table 17.6.2.1Heat detector temperature classes and color codes; 20°F ruleInitiating
NFPA 72 §17.6.3.1Heat detectors on smooth ceilings: spacing S, 0.7S, and 4 in. / 12 in. locationInitiating
NFPA 72 §17.6.3.2 – §17.6.3.4Heat: solid joists (50 percent), beams, and sloped ceilings (36 in. from the peak)Initiating
NFPA 72 Table 17.6.3.5.1Heat detector spacing reduction for ceiling height (above 10 ft)Initiating
NFPA 72 §17.7.1Smoke: environmental conditions (32–100°F, 93 percent RH, 300 ft/min)Initiating
NFPA 72 §17.7.2Protection of detectors during constructionInitiating
NFPA 72 §17.7.4.2Spot-type smoke: location (12 in.), 30 ft / 0.7S spacing, beams and joistsInitiating
NFPA 72 §17.7.4.6 / §17.7.4.7Air-sampling (120 s) and projected beam detectorsInitiating
NFPA 72 §17.7.5HVAC: do not locate where airflow prevents operationInitiating
NFPA 72 §17.7.6Duct detectors and door release detectorsInitiating
NFPA 72 Table 17.7.7.3.3.2Smoke detector spacing in high air movement areasInitiating
NFPA 72 §17.8 / §17.9Flame detectors; combination, multi-criteria, and multi-sensor detectorsInitiating
NFPA 72 §17.12Carbon monoxide (CO) detectorsInitiating
NFPA 72 §17.13Sprinkler waterflow: activation within 90 sInitiating
NFPA 72 §17.15Manual boxes: 42–48 in., 5 ft from the exit, 200 ft travelInitiating
NFPA 72 §17.17Supervisory: valves (2 revolutions or 1/5), pressure, level, and temperatureInitiating
NFPA 72 §14.4.4.3Smoke detector sensitivity testingInitiating
NFPA 72 Table 14.4.3.2Test methods and frequencies for initiating devicesInitiating
NFPA 72-2022 §18.3General: listing, nameplate, mechanical protection (§18.3.4), mounting (§18.3.5), connections (§18.3.6), NAC (§18.3.7)Notification
NFPA 72-2022 A.18.3.7.1NAC design: 24 VDC appliances operate from 16 to 33 VDC; maximum listed current; voltage dropNotification
NFPA 72-2022 §18.4.1Audible general: ambient over 105 dBA → visual appliances; 110 dBA maximum; documentation of design levelsNotification
NFPA 72-2022 §18.4.2Temporal-3 evacuation signal (ANSI/ASA S3.41); 2022 duration rule; synchronizationNotification
NFPA 72-2022 §18.4.3Temporal-4 CO signalNotification
NFPA 72-2022 §18.4.4Public mode: 15 dB / 5 dB, 5 ft, dBA; elevators, restrooms, ambient noise reductionNotification
NFPA 72-2022 §18.4.5Private mode: 10 dB / 5 dBNotification
NFPA 72-2022 §18.4.6Sleeping areas: 75 dBA at the pillow, barriers, 520 HzNotification
NFPA 72-2022 §18.4.8Exit marking audible notification appliancesNotification
NFPA 72-2022 §18.4.9Audible location: 90 in. / 6 in.; combination A/V per §18.5.5Notification
NFPA 72-2022 §18.5.3Flash rate 1 to 2 Hz, clear or white light, 1000 cd maximumNotification
NFPA 72-2022 §18.5.5.1Wall-mounted visual: entire lens between 80 and 96 in.; low ceilingsNotification
NFPA 72-2022 §18.5.5.5Ceiling-listed visual: minimum 80 in. or the ceiling height (2022)Notification
NFPA 72-2022 Table 18.5.5.7.1(a)Room spacing: wall-mounted visual appliances (candela by room size)Notification
NFPA 72-2022 Table 18.5.5.7.1(b)Room spacing: ceiling-mounted visual appliances (10, 20, or 30 ft ceiling height)Notification
NFPA 72-2022 §18.5.5.7.2Synchronization: more than two appliances in the field of viewNotification
NFPA 72-2022 §18.5.5.8Corridors 20 ft wide or less: 15 cd, 15 ft from each end, 100 ft between appliancesNotification
NFPA 72-2022 §18.5.5.10Sleeping rooms: 110 or 177 cd by distance from the ceiling (24 in.); within 16 ft of the pillowNotification
NFPA 72-2022 Table 14.4.3.2Testing: alarm notification appliances (audible, textual, visual) and exit markingNotification
NFPA 72 §12.3Pathway classes A, B, C, D, E, N, and XCircuits/Sys.
NFPA 72 §12.3.8 / §12.3.8.1Separate outgoing and return routing (Class A, N, X); 10 ft, single-drop, and ≤ 1000 ft² room exceptionsCircuits/Sys.
NFPA 72 A.12.3.8Recommended separation 12 in. vertical / 48 in. horizontal (annex)Circuits/Sys.
NFPA 72 §12.4 and Table A.12.4Survivability levels 0 to 4 (Level 4 new in 2022)Circuits/Sys.
NFPA 72 §12.6.1Monitoring for integrity: open or ground indicated within 200 sCircuits/Sys.
NFPA 72 §12.2.3Optical fiber (NEC 770/760/840) and installation per manufacturer's instructionsCircuits/Sys.
NFPA 72 §21.2.4Interface device within 3 ft (1 m) of the controlled componentCircuits/Sys.
NFPA 72 §21.3Elevator Phase I recall: designated level, alternate level, and 'fire hat'Circuits/Sys.
NFPA 72 §21.4Elevator power shutdown (shunt trip): 2 ft, no time delay, voltage supervisionCircuits/Sys.
NFPA 72 §23.8.1Pre-signal and positive alarm sequence (15 s / 180 s)Circuits/Sys.
NFPA 72 §23.8.5.4Alarm verification (60 s max.)Circuits/Sys.
NFPA 72 §23.10.2Partial evacuation: a fire in one zone does not affect other zonesCircuits/Sys.
NFPA 72 §24.3.14Pathway survivability for emergency communications systemsCircuits/Sys.
NFPA 72 §26.3.8Central station responses: alarm, supervisory, trouble (runner 2 h / 4 h)Circuits/Sys.
NFPA 72 §26.6.3Performance-based technologies (IP/cellular): 60 min / 6 hCircuits/Sys.
NFPA 72 §26.6.4DACT: second transmission means, channel tests, 90 s per attemptCircuits/Sys.
NFPA 72 Ch. 7 (§7.3)Design documentation: pathway classes and survivability levelsCircuits/Sys.
NFPA 72-2022 §10.6.7.2.1Secondary capacity: 24 h standby + 5 min alarm (15 min for EVACS)Electricity
NFPA 72-2022 §7.2.1Minimum documentation: battery and NAC voltage drop calculationsElectricity
NFPA 72-2022 Table 14.4.3.2Conductor tests (1 V stray voltage, ground, short, loop resistance) and battery testsElectricity
NFPA 72-2022 §10.3Equipment listed, installed per the manufacturer, and compatibleElectricity
NFPA 72-2022 Ch. 12Circuits and pathways: Class A/B, monitoring for integrity, ground faultsElectricity
NFPA 72 §14.2.2Impairments, deficiencies (written notice within 24 h), recalls, and observationsITM Ch. 14
NFPA 72 §14.2.3Owner responsibility and delegationITM Ch. 14
NFPA 72 §14.2.4Notification before and after testingITM Ch. 14
NFPA 72 §14.2.6Testing of releasing systemsITM Ch. 14
NFPA 72 §14.2.10Written test planITM Ch. 14
NFPA 72 Table 14.3.1Visual inspection: frequencies and methodsITM Ch. 14
NFPA 72 §14.4.2Reacceptance: 100% affected + 10% (max. 50); executive software; remote changesITM Ch. 14
NFPA 72 Table 14.4.3.2 items 2–4Control unit, trouble signals, ground fault, transmission (DACT 90 s / 4 min)ITM Ch. 14
NFPA 72 Table 14.4.3.2 items 8–9Secondary power (5/15 min) and VRLA batteriesITM Ch. 14
NFPA 72 Table 14.4.3.2 item 17Initiating devices: methods and frequenciesITM Ch. 14
NFPA 72 Table 14.4.3.2 items 22–24Notification appliances and emergency control functionsITM Ch. 14
NFPA 72 §14.4.4.3Smoke detector sensitivity (1 year, every alternate year, up to 5)ITM Ch. 14
NFPA 72 A.14.4.3.2Annex: ohmic test and battery capacity calculationITM Ch. 14
NFPA 72 §14.6Records: retention and owner documentsITM Ch. 14
NFPA 72 §7.6.6 / Fig. 7.8.2(g)System Record of Inspection and TestingITM Ch. 14
NFPA 72 §10.5.3Qualifications of inspection, testing, and service personnelITM Ch. 14
NFPA 72 Section 10.21System impairmentsITM Ch. 14
NFPA 72 §10.3.3Devices powered by the IDC/SLC must be listed for use with the control unit (2-wire compatibility)Repair
NFPA 72 §10.6.5Dedicated branch circuit: red marking, restricted access, 'FIRE ALARM CIRCUIT'Repair
NFPA 72 §10.6.10Secondary batteries: month/year of manufacture markingRepair
NFPA 72 §10.21Impairments: notify owner, report to AHJ if >8 h, keep record 1 year, notify when endedRepair
NFPA 72 §12.3.1 / §12.3.2Class A and Class B performance with an open and a ground faultRepair
NFPA 72 §12.3.8Class A: outgoing and return conductors routed separately (10 ft, 1000 ft² exceptions)Repair
NFPA 72 §12.6.1Monitoring for integrity: open or ground annunciated within 200 sRepair
NFPA 72 §14.2.2Impairments, deficiencies (in writing within 24 h), and observationsRepair
NFPA 72 §14.2.4Notification before and after testingRepair
NFPA 72 §14.4.2 and A.14.4.2Reacceptance: added, deleted, FACU hardware, software (10%, max. 50)Repair
NFPA 72 Table 14.4.3.2 item 2Control unit: functions, fuses (rating and supervision), LEDs, primary powerRepair
NFPA 72 Table 14.4.3.2 item 9VRLA: temperature (18°F), charger, 13.26 V per unit, ohmic, 3 years / load testRepair
NFPA 72 Table 14.4.3.2 item 15Conductors: stray voltage ≤ 1 V, ground, shorts, loop resistance, 10% circuit integrityRepair
NFPA 72 Table 14.4.3.2 item 17Initiating devices: nonrestorable heat at 15 years, valves 2 revolutions or 1/5, ASD, projected beamRepair
NFPA 72 §14.4.4.3Smoke detector sensitivity: 1 year, every alternate year, up to 5 years; out of range → clean or replaceRepair
NFPA 72 §14.6Inspection, testing, and maintenance records (retention)Repair
NFPA 72 §17.6.2 / Table 17.6.2.1Heat detector temperature classification and color code (+20°F above ceiling)Repair
NFPA 72 §17.7.1.8Smoke detector ambient limits (32–100°F, 93% RH, 300 ft/min)Repair
NFPA 72 §17.7.4.6 / §17.7.4.7Air sampling detectors (120 s transport) and projected beam detectors (stable mounting)Repair
NFPA 72 §7.2.1Minimum required documentation (17 items)Documents
NFPA 72 §7.3.3Design documents: pathway class and survivabilityDocuments
NFPA 72 §7.4.2–7.4.4Scale, basis for record drawings, general information, and NFPA 170 symbolsDocuments
NFPA 72 §7.4.5Floor plan drawing contentsDocuments
NFPA 72 §7.4.6Riser diagram contentsDocuments
NFPA 72 §7.4.7Control unit diagramsDocuments
NFPA 72 §7.4.8–7.4.10Typical wiring, sequence of operation, and calculationsDocuments
NFPA 72 §7.5.3Documents delivered to the ownerDocuments
NFPA 72 §7.5.5Record (as-built) drawingsDocuments
NFPA 72 §7.5.6Record of completion: who completes it, revisions, electronic formatDocuments
NFPA 72 §7.5.7Site-specific software and passwordsDocuments
NFPA 72 §7.6.6Record of inspection and testingDocuments
NFPA 72 §7.7Records, SYSTEM RECORD DOCUMENTS cabinet, and securityDocuments
NFPA 72 §7.8.2Forms, Figures 7.8.2(a) through 7.8.2(m)Documents
NFPA 72 §14.6Permanent records and ITM record retentionDocuments
NFPA 72 Figure A.14.6.1.1Typical input/output matrixDocuments
NFPA 72 §10.3.3Devices listed for use with the control unit (compatibility)Documents
NFPA 72 Table 17.6.3.5.1Heat detector spacing reduction by ceiling height (multipliers)Community

NFPA 70 / NEC (2020)

SectionWhyChapter
NFPA 70 760.41(B) / 760.121(B)Branch-circuit identification: red, plus the 'FIRE ALARM CIRCUIT' legendFundamentals
NEC 2020 §760.2Definitions: PLFA, NPLFA, abandoned cable, CI cableNEC 760
NEC 2020 §760.3Other articles that apply (300.21, 300.22, Art. 725, Art. 770)NEC 760
NEC 2020 §760.21Access: cables must not prevent removal of ceiling panelsNEC 760
NEC 2020 §760.24Workmanship, support, plenum cable ties; CI supported every 24 in. with steelNEC 760
NEC 2020 §760.25Abandoned cables and future-use tagsNEC 760
NEC 2020 §760.41 / §760.121FACU branch circuit: no other loads, no GFCI/AFCI, red, 'FIRE ALARM CIRCUIT'NEC 760
NEC 2020 §760.43NPLFA protection: 7 A (18 AWG), 10 A (16 AWG)NEC 760
NEC 2020 §760.49NPLFA conductors: Table 402.5, 600 V insulationNEC 760
NEC 2020 §760.53NPLFA cables: NPLF, NPLFR, NPLFPNEC 760
NEC 2020 §760.127Supply side of a PLFA source: 20 A max. protectionNEC 760
NEC 2020 §760.130PLFA load-side methods: 18 in. below 7 ft, floor/wall penetrations, hoistways, splices, reclassificationNEC 760
NEC 2020 §760.136Separation from power: barriers, 1/4 in. in enclosures, 2 in. in open runsNEC 760
NEC 2020 §760.139PLFA with Class 2/3 and communications; audio prohibitedNEC 760
NEC 2020 §760.143Do not use the outside of raceways as supportNEC 760
NEC 2020 Table 760.154 and 760.154(A)PLFA cable applications and substitution hierarchyNEC 760
NEC 2020 §760.179PLFA listing and marking: 300 V, FPLP/FPLR/FPL, CI, no voltage markingNEC 760
NEC 2020 §300.4 and §300.11Protection against nails (1¼ in., 1/16 in. plate) and support above suspended ceilingsNEC 760
NEC 2020 §300.21 and §300.22Firestopping penetrations and environmental air spaces (plenums)NEC 760
NEC 2020 Table 110.26(A)(1)Working space in front of the FACU (3 ft at 0–150 V)NEC 760
NEC 2020 Table 314.16(B)Volume allowance per conductor for box fillNEC 760
NEC 2020 Ch. 9, Table 8Conductor properties: cmil and dc resistance at 75°C (Ω/kft), solid and strandedElectricity
NEC 2020 Ch. 9, Table 1Percent fill: 1 conductor 53%, 2 conductors 31%, over 2: 40%Electricity
NEC 2020 Ch. 9, Notes to TablesNote 4 (nipples ≤ 24 in.: 60%), Note 7 (round up at ≥ 0.8), Note 9 (multiconductor cable = 1 conductor)Electricity
NEC 2020 Ch. 9, Table 4Conduit and tubing dimensions and areas by type (EMT, PVC, RMC...) at 40/53/31/60%Electricity
NEC 2020 Ch. 9, Table 5Dimensions and areas of insulated conductors (THHN, TFFN...)Electricity
NEC 2020 Ch. 9, Table 9AC resistance and reactance (do not confuse with Table 8, dc)Electricity
NEC 2020 Annex CMaximum number of same-size conductors per raceway (C.1 = EMT)Electricity
NEC 2020 760.30, 760.41(B), 760.154Circuit identification, FACU branch circuit, PLFA cable substitutionRepair
NEC 2020 Ch. 9, Table 8Conductor properties: cmil and resistanceDocuments
NEC Annex C, Table C.1Maximum conductors of one size in EMTCommunity
NEC Table 314.16(A) and (B)Box volumes and volume per conductorCommunity
NEC 760.53(A)(1) / 760.130(B)(1)Exposed cable within 7 ft of the floor: fasten every 18 in.Community

Ugly’s Electrical References (2020)

SectionWhyChapter
Ugly's 2020 – Ohm's Law / Power FormulasE, I, R, P formula wheelElectricity
Ugly's 2020 – Series and Parallel CircuitsResistance, current, and voltage in series and in parallelElectricity
Ugly's 2020 – Voltage Drop CalculationsVD = 2 × K × I × L ÷ CM (1φ) and 1.732 × K × I × L ÷ CM (3φ); K = 12.9 Cu, 21.2 AlElectricity
Ugly's 2020 – distribution systems120/240 V single-phase, 208Y/120 V, and 480Y/277 VElectricity
Ugly’s: electrical symbolsSchematic symbols for resistor, capacitor, battery, ground, diode, coilCommunity

Study-only references (not allowed in the test center)

SectionWhyChapter
29 CFR 1926.1053(b)(1)Side rails 3 ft above the upper landing surfaceSafety
29 CFR 1926.1053(b)(5)(i)1:4 angle (base = ¼ of the working length)Safety
29 CFR 1926.1053(b)(12)–(16)Nonconductive near energized parts; no standing on the top cap; inspection and Do Not Use tagSafety
29 CFR 1926.1051(a)Stairway or ladder at a break in elevation of 19 in. or moreSafety
29 CFR 1926.451(a)(1), (e)(1), (g)(1)Scaffolds: 4 × load, access above 2 ft, fall protection above 10 ftSafety
29 CFR 1926.451(g)(4)(ii)Scaffold guardrail 38–45 in.Safety
29 CFR 1926.453(b)(2)Aerial lifts: daily control test, tie off to the boom or basketSafety
29 CFR 1926.501(b)(1) / 1910.28(b)(1)Fall protection trigger: 6 ft / 4 ftSafety
29 CFR 1926.502(b), (d), (i)Guardrail 42 ± 3 in. and 200 lb; anchorage 5,000 lb; free fall 6 ft; hole coversSafety
29 CFR 1910.147(d), (e)(3), (f)(3)Lockout steps, lock removal, group lockoutSafety
29 CFR 1910.333(b)(2), (c)(8)Electrical lockout, verification, conductive jewelrySafety
29 CFR 1926.404(b)(1)GFCI or AEGCP on construction sitesSafety
29 CFR 1926.405(a)(2), (g)Extension cords and flexible cordsSafety
29 CFR 1910.95, Table G-16Noise: 85 dBA action level, 90 dBA PELSafety
29 CFR 1926.102 / 1910.134Z87.1 eye protection; respiratorsSafety
29 CFR 1910.1200(f), (g)GHS labels and 16-section SDSSafety
29 CFR 1926.1153, Table 1Silica: controls for drillsSafety
29 CFR 1910.146Permit-required confined spacesSafety
29 CFR 1926.150(c)Construction site extinguishers: 2A per 3,000 ft², 100 ftSafety
Red Cross CPR/AED100–120/min, ≥ 2 in., 30:2, AEDSafety

Practice for the real thing. Take the free 20-minute Level I practice exam (no account needed), or get lifetime access to 85-question exams in the NICET format and 552 Level I questions with explanations.