Inspection, Testing and Maintenance (NFPA 72-2022 Ch. 14)

NFPA 72-2022 Ch. 14 · NFPA 72-2022 Ch. 7 (documentation) · NFPA 72-2022 Ch. 10 (personnel, impairments) · NFPA 72-2022 Annex A.14 · Outline tasks 1.2.1, 1.2.2, 1.3.1

What NICET expects at Level I

The Maintenance domain (1.2) is worth 40–50% of the exam, and almost all of it comes from Chapter 14 of NFPA 72-2022. A Level I technician must know how often each component is inspected and tested, how it is tested (the Method column of the table), what to do when something fails (repair or replace, and notify), and which records must be kept. The exam is open book with the printed code: the candidate who can open to the right table row in under a minute wins. Learn the structure of the chapter, not the wording.

Map of Chapter 14 (2022 edition)

SectionKey content
14.2.2Impairments, deficiencies (written notice within 24 h), and observations (new in 2022)
14.2.3Responsibility of the owner or the owner's designated representative
14.2.4Notification before testing and when testing is concluded
14.2.6Releasing systems: secure the suppression system, no discharge
14.2.10Written test plan
14.3 and Table 14.3.1Visual inspection: frequency and method
14.4.2Reacceptance testing (hardware and software)
Table 14.4.3.2Testing: method and periodic frequency
14.4.4Testing frequency; 14.4.4.3 smoke detector sensitivity
14.5Maintenance
14.6Records
Edition trap: older editions had a separate Table 14.4.5 (Testing Frequencies); it no longer exists. In 2022 the testing frequencies are in the Periodic Frequency column of Table 14.4.3.2 (Testing). A lot of older study material still cites Table 14.4.5.

Visual inspection: Table 14.3.1

ComponentFrequency
All equipment (building changes, obstructions, damage, cleanliness)Annual
Monitored control unit: fuses, interfaced equipment, lamps/LEDs, primary power supplyAnnual
Monitored control unit: trouble signalsSemiannual
Control unit NOT monitored (all of the above)Weekly
Manual boxes, heat and smoke detectors, duct detectors (general)Semiannual
Radiant energy (flame) and video image detectorsQuarterly
Waterflow devices and supervisory signal devices (tamper)Semiannual (quarterly before 2022)
Audible and visible notification appliancesSemiannual
VRLA batteries: month/year of manufacture markingSemiannual
Supervising station transmitters (DACT, DART, RAT)Annual
NAC extenders and remote power suppliesAnnual

Testing: Table 14.4.3.2 (most-asked frequencies)

Component (item)Frequency
Control unit: functions, fuses, lamps, primary power supply (2)Annual
Ground fault and transmission to the off-premises station (3)Annual
Secondary power: 5 min in alarm for general alarm, 15 min for voice (8)Annual
VRLA batteries: temperature, charger, unit voltage, ohmic (9)Semiannual
VRLA batteries: replacement or load test (9)Every 3 years
Manual boxes, smoke functional, heat, duct, projected beam, CO (17)Annual
Flame detectors (17)Semiannual
Control valve switch (17)Semiannual
Air pressure, room temperature, water level, and water temperature switches (17)Annual
Waterflow devices (17)Semiannual
Notification appliances (22) and emergency control functions (24)Annual
Dedicated engine-driven generator, by the owner per NFPA 110 (6)Monthly

Methods you must know

VRLA batteries (Table 14.4.3.2, item 9)

TestReplacement criterion
Temperature (negative terminal, infrared thermometer)More than 18°F (10°C) above the enclosure's internal ambient temperature
Cell/unit voltage (fully charged, on the charger)Less than 13.26 V
Ohmic (against baseline)Deviation of 30% or more (conductance) or 40% or more (resistance/impedance)
Load test (every 3 years)80% or less: replace; less than 85%: replace at the next scheduled test

Before testing batteries, make sure any software held in volatile memory is protected. A bulging, cracked, or leaking battery is replaced, not tested. Vented lead-acid and nickel-cadmium batteries no longer have their own rows: they follow the manufacturer's instructions or IEEE 450 / IEEE 1106.

Reacceptance (14.4.2)

Example: 600 initiating devices, 30 affected. Test the 30, plus 10% of 570, which is 57; with the cap of 50, the total is 80 devices.

Notifications, deficiencies, and impairments

Records (14.6 and Ch. 7)

Common traps: (1) Confusing visual inspection (Table 14.3.1) with testing (Table 14.4.3.2). (2) In 2022, waterflow and supervisory devices have a semiannual visual inspection, not quarterly. (3) Sensitivity is never measured with an unmeasured aerosol. (4) The 10% / maximum 50 rule is for initiating devices NOT affected; affected devices are tested 100%. (5) NFPA 72 requires testing the emergency control function interface device, not the whole controlled function (for example, the elevator). (6) Control valve switch: semiannual; the other supervisory switches: annual.

How to find it fast in the printed code book

  1. Does the question say look at or inspect? Turn to Table 14.3.1. Does it say test? Turn to Table 14.4.3.2. Its items are numbered: 2 control unit, 3 trouble signals and ground fault, 4 transmission equipment, 8 secondary power, 9 VRLA, 15 conductors, 17 initiating devices, 22 notification appliances, and 24 emergency control functions.
  2. Table 14.4.3.2 runs for many pages. Place permanent tabs at its first page, at item 9 (batteries), at item 17 (initiating devices), and at item 22 (notification appliances), plus one tab on Table 14.3.1.
  3. Other tabs worth placing: 14.4.2 (reacceptance), 14.4.4.3 (sensitivity), 14.6 and 7.6.6 (records), 10.5.3 (personnel), and 10.21 (impairments).
  4. Use the index at the back of the book: look up "Sensitivity testing", "Reacceptance testing", "Impairments", "Batteries", "Records". Every section number starts with its chapter (14.x is Chapter 14). An asterisk (*) next to a section means Annex A has explanatory material (A.14.x) — not mandatory, but it explains intent, such as A.14.4.2 (like-for-like replacement) and A.14.4.3.2 (battery formulas).
  5. Highlight the key numbers in the Method column before exam day: "two revolutions", "18°F", "13.26 V", "50 devices", "1 year thereafter".
  6. Read every frequency word (weekly, monthly, quarterly, semiannually, annually) from the Periodic Frequency column of Table 14.3.1 or Table 14.4.3.2, and count each interval from the date of the last inspection or test: semiannual items come due about 6 months later and annual items about 12 months later.

What to tab in your books

SectionWhy
NFPA 72 §14.2.2Impairments, deficiencies (written notice within 24 h), recalls, and observations
NFPA 72 §14.2.3Owner responsibility and delegation
NFPA 72 §14.2.4Notification before and after testing
NFPA 72 §14.2.6Testing of releasing systems
NFPA 72 §14.2.10Written test plan
NFPA 72 Table 14.3.1Visual inspection: frequencies and methods
NFPA 72 §14.4.2Reacceptance: 100% affected + 10% (max. 50); executive software; remote changes
NFPA 72 Table 14.4.3.2 items 2–4Control unit, trouble signals, ground fault, transmission (DACT 90 s / 4 min)
NFPA 72 Table 14.4.3.2 items 8–9Secondary power (5/15 min) and VRLA batteries
NFPA 72 Table 14.4.3.2 item 17Initiating devices: methods and frequencies
NFPA 72 Table 14.4.3.2 items 22–24Notification appliances and emergency control functions
NFPA 72 §14.4.4.3Smoke detector sensitivity (1 year, every alternate year, up to 5)
NFPA 72 A.14.4.3.2Annex: ohmic test and battery capacity calculation
NFPA 72 §14.6Records: retention and owner documents
NFPA 72 §7.6.6 / Fig. 7.8.2(g)System Record of Inspection and Testing
NFPA 72 §10.5.3Qualifications of inspection, testing, and service personnel
NFPA 72 Section 10.21System impairments

Chapter vocabulary

Inspection
Visual examination of equipment to verify its location and condition and that nothing has changed or been damaged (Table 14.3.1).
Testing
Operating a device or system to prove that it works, using the method in Table 14.4.3.2.
Maintenance
Work done to keep equipment operable per the manufacturer's instructions (Section 14.5).
Impairment
A condition in which the system or part of it is out of order or cannot perform its function; requires notification and mitigating measures.
Deficiency
A condition that affects system performance; it must be corrected and, if not corrected at the end of the visit, reported in writing within 24 h.
Observation
A suggested improvement that is neither an impairment nor a deficiency; the owner is not required to act on it (new in 2022).
Reacceptance testing
Testing after components, wiring, or software are added, deleted, repaired, or modified (14.4.2).
Site-specific software
Programming unique to the installation (input/output mapping, labels, control matrix).
Executive software
The control unit manufacturer's firmware or operating system; a change requires a 10% functional test.
Sensitivity testing
Verification with a calibrated method that a smoke detector is within its listed and marked range.
Valve-regulated lead-acid (VRLA) battery
Sealed battery typical of fire alarm panels; tested semiannually and replaced or load tested every 3 years.
Ohmic test
Measurement of a battery's internal conductance, resistance, or impedance, compared with a baseline value.
Inspector's test connection
Sprinkler system outlet that simulates the flow of one sprinkler to test the waterflow switch.
Control valve supervisory switch (tamper)
Sends a supervisory signal when the valve is closed; must operate within 2 revolutions or 1/5 of the travel.
Emergency control function interface device
Relay or module through which the fire alarm acts on elevators, HVAC, or doors; NFPA 72 requires this device to be tested.
Record of completion
Document for the completed installation (Fig. 7.8.2(a)); revised after software changes.
Record of inspection and testing
Form in Fig. 7.8.2(g) and its supplements, or an equivalent alternative record, used to document periodic ITM.
Test plan
Written document that clearly establishes the scope of the testing (14.2.10).
Designated representative
Person or company to whom the owner assigns ITM responsibility by contract or lease.
Fire watch
Approved mitigating measure: personnel who patrol the building while the system is out of service.
Nonrestorable heat detector
Detector whose sensing element is destroyed when it operates; it is not heat tested in the field.
Supervising station
Facility that receives alarm, supervisory, and trouble signals; it must be notified before and after testing.
Periodic frequency
How often a component is inspected (Table 14.3.1) or tested (Table 14.4.3.2): weekly, monthly, quarterly, semiannually, annually, or at a multi-year interval; count the interval from the date of the last inspection or test.

93 practice questions cover this chapter, each with an explanation and the code section. Get lifetime access or try the free practice exam.