Community-Reported Topics
NFPA 72-2022 Ch. 17 · NEC 2020 Ch. 9, Annex C, 314.16, 760 · Ugly’s 2020 · OSHA 1926 · Outline tasks 1.1.1, 1.1.2, 1.1.3, 1.2.2, 1.3.1
People preparing for FAS Level I share what they study in public flashcard decks (mostly on Quizlet) and in forums such as The Fire Panel and Mike Holt. Reading them shows which topics keep coming up. This chapter has original questions on the topics those decks repeat that the other chapters covered only lightly: counting detectors in a room, the ceiling-height reduction table, conduit and box fill, series-parallel circuits, schematic symbols and reading a plan with a legend.
Why the deck questions are not copied here. Several decks look like questions remembered from real NICET exams. Candidates accept a non-disclosure agreement, so sharing exam items breaks NICET rules and can cost a certification. Many deck answers are also wrong or out of date for the 2022/2020 editions (see the table below). The questions in this chapter test the same skills with different numbers and scenarios.
Common errors in community decks
| What some decks say | What the exam editions say | Where |
|---|---|---|
| Waterflow devices are tested annually | Semiannually | NFPA 72-2022 Table 14.4.3.2 |
| Exposed fire alarm cable within 7 ft of the floor is fastened every 24 in. | Every 18 in. or less | NEC 2020 760.53(A)(1), 760.130(B)(1) |
| Abandoned cable kept for future use is “secured to the conduit” | It must be tagged for future use (otherwise the accessible portion is removed) | NEC 2020 760.25 |
| Test frequencies are in Table 14.4.5 | Table 14.4.3.2, column “Periodic Frequency” | NFPA 72-2022 |
| Notify the AHJ when a system is out of service 4 hours | NFPA 72 uses more than 8 hours; the 4-hour fire watch comes from NFPA 101/IFC | NFPA 72-2022 §10.21 |
| Smoke detectors need 4 in. of “dead air” from the wall | Only heat detectors keep the 4 in. rule; smoke detectors may be on the wall within 12 in. of the ceiling | NFPA 72-2022 §17.6.3.1.3, §17.7.4.2 |
| DACT test signal every 24 hours | At least every 6 hours | NFPA 72-2022 §26.6.4 |
| Ladder base 1 ft out for every 4 ft of height | Horizontal distance ≈ 1/4 of the working length (the length along the ladder) | OSHA 1926.1053(b)(5)(i) |
Skills these decks emphasize
Counting detectors in a rectangular room
- Find the spacing S: the listed spacing for heat detectors (reduced for ceilings above 10 ft with Table 17.6.3.5.1), or 30 ft nominal for smoke detectors on smooth ceilings.
- Divide each room dimension by S and round up to the next whole number.
- Multiply the two results. Example: 75 × 50 ft with S = 30 ft → 3 × 2 = 6 detectors.
Heat detector spacing reduction for high ceilings (Table 17.6.3.5.1)
For ceilings above 10 ft and up to 30 ft, multiply the listed spacing by the factor for the ceiling height. Examples verified for the exam edition: 14–16 ft → 0.77; 24–26 ft → 0.46; 28–30 ft → 0.34. At 10 ft or lower there is no reduction. The table applies to heat detectors, not smoke detectors.
Conduit fill and box fill
- When all conductors are the same size and type, read NEC Annex C directly (Table C.1 is EMT). Example: 1/2 in. EMT holds 12 #14 THHN or 9 #12 THHN.
- Box fill: each conductor counts its volume from Table 314.16(B): 18 AWG 1.50 in³, 16 AWG 1.75 in³, 14 AWG 2.00 in³. Compare the total with the box volume in Table 314.16(A), e.g., 4 × 1-1/2 in. square = 21.0 in³, 4 × 2-1/8 in. square = 30.3 in³.
Series-parallel circuits
Reduce the parallel group first (two equal resistors in parallel = half of one), add the series resistance, find the total current with Ohm’s law, then work back to each resistor. Current is the same in series parts; voltage is the same across parallel branches.
Plans and symbols
Always read the legend before counting devices: symbols vary between design firms. Schematic symbols (resistor, capacitor, battery, ground, diode, coil) are in the reference pages of Ugly’s.
Where these resources are
- Quizlet decks for NICET FAS Level I — useful to see topics; check every answer against the 2022/2020 editions.
- The Fire Panel forum: tips for NICET 1 — advice: know what each chapter contains, and use the index and annex.
- Mike Holt forum: best NICET fire alarm test prep — candidates recommend tabbed books and the NTC “Red Book”.
- NICET sells two official practice tests in its online store; they are the only practice items written by NICET.
What to tab in your books
| Section | Why |
|---|---|
| NFPA 72 Table 17.6.3.5.1 | Heat detector spacing reduction by ceiling height (multipliers) |
| NEC Annex C, Table C.1 | Maximum conductors of one size in EMT |
| NEC Table 314.16(A) and (B) | Box volumes and volume per conductor |
| NEC 760.53(A)(1) / 760.130(B)(1) | Exposed cable within 7 ft of the floor: fasten every 18 in. |
| Ugly’s: electrical symbols | Schematic symbols for resistor, capacitor, battery, ground, diode, coil |
Chapter vocabulary
- Listed spacing
- The maximum distance between heat detectors determined by the testing laboratory and printed on the detector’s listing; reduced for high ceilings and joists.
- Single-action manual box
- A manual fire alarm box that sends an alarm with one motion, such as pulling the handle.
- Double-action manual box
- A manual fire alarm box that needs two motions, such as lifting or pushing a cover and then pulling the handle.
- Normally open (N.O.) contact
- A contact that is open at rest and closes when the device operates; the usual alarm contact of conventional initiating devices.
- Box fill
- The total volume taken by conductors, devices and fittings in an outlet or junction box, which must not exceed the box volume (NEC 314.16).
- Legend
- The key on a drawing that defines each symbol used; read it before counting or locating devices.
26 practice questions cover this chapter, each with an explanation and the code section. Get lifetime access or try the free practice exam.
More Level I study guides
- 8-week study plan
- Fundamentals and Definitions
- Initiating Devices
- Notification Appliances
- Circuits, Systems, and Control Functions
- NEC 2020 (NFPA 70): Article 760 and Wiring Methods
- Basic Electricity and Calculations
- Inspection, Testing and Maintenance
- Troubleshooting, Repair and Device Replacement
- Job Site Safety: OSHA 1910/1926 and First Aid
- Technical Documents, Drawings, and Submittals
- Community-Reported Topics
- Level I tabbing guide for your printed code books
- Strategy with printed code books
- Key numbers (NFPA 72 · NEC · OSHA)
- Formulas and conversions
- Fire alarm glossary for the NICET exams