Basic Electricity and Calculations (Ugly's / NEC Ch. 9)

Ugly's Electrical References 2020 (Ohm's law, power, series/parallel, voltage drop) · NEC 2020 Ch. 9 (Tables 1, 4, 5, and 8; Notes to Tables) and Annex C · NFPA 72-2022 §7.2.1, §10.6.7.2.1, and Table 14.4.3.2 · Outline tasks 1.1.2, 1.2.2, 1.3.1, 1.1.1

What NICET expects at Level I

At Level I, electrical calculations show up mainly in tasks 1.1.2 (cabling and infrastructure) and 1.2.2 (repair or replace). You are not asked to design but to verify: add up NAC currents, calculate voltage drop, check the voltage at the last appliance, size batteries, and use a multimeter correctly. Tools: the on-screen exam calculator, Ugly's Electrical References, NEC 2020 Chapter 9, and NFPA 72-2022.

Formula sheet

ConceptFormulaNote
Ohm's lawE = I × R; I = E ÷ R; R = E ÷ IUgly's uses E for voltage
Power (watts)P = E × I = I² × R = E² ÷ RUgly's formula "wheel"
Resistors in seriesRT = R1 + R2 + ...The same current flows through the whole loop
Resistors in parallel1/RT = 1/R1 + 1/R2 + ...; equal values: R ÷ nThe same voltage across each branch
Kirchhoff (currents)IT = I1 + I2 + ...Total current of a NAC
Kirchhoff (voltages)E source = sum of dropsV at last appliance = starting V − VD
DC voltage drop, 2-wire (K method)VD = 2 × K × I × L ÷ CMK = 12.9 copper, 21.2 aluminum (Ugly's); L = one-way distance
Voltage drop (resistance method)VD = I × (Ω/kft × 2L ÷ 1000)Ω/kft from NEC Ch. 9, Table 8
Three-phase drop (Ugly's)VD = 1.732 × K × I × L ÷ CMRarely used in fire alarm
BatteriesAh = (I standby × 24 h) + (I alarm × 5/60 h), then × marginNFPA 72-2022 §10.6.7.2.1; EVACS: 15/60 h

Prefixes: 1 mA = 0.001 A; 1 kΩ = 1000 Ω; 1 MΩ = 1,000,000 Ω; 1 mW = 0.001 W. Always convert mA to A before multiplying. 5 min = 0.0833 h; 15 min = 0.25 h.

NEC 2020 Ch. 9, Table 8: values to keep handy

DC resistance at 75°C (167°F), uncoated copper, in ohms per 1000 ft. Values checked against Table 8; for these sizes they have not changed in recent NEC editions.

AWGArea (cmil)Solid (Ω/kft)Stranded, 7 strands (Ω/kft)
1816207.777.95
1625804.894.99
1441103.073.14
1265301.931.98
1010,3801.211.24

Coated copper has slightly higher resistance (for example, 14 AWG stranded coated = 3.26 Ω/kft). Quick rule: smaller AWG number = thicker conductor = less resistance = less voltage drop.

About the K value: Ugly's uses K = 12.9 Ω·cmil/ft for copper (equivalent to the resistance at 75°C). Other texts use 10.4 or 10.7 (copper at about 20–25°C), which give smaller drops. On the exam, use the K the question gives; if none is given, use 12.9 or Table 8. Both methods agree: 12.9 ÷ 4110 cmil × 1000 ≈ 3.14 Ω/kft, the same as 14 AWG stranded. This question bank uses K = 12.9.

Worked example: NAC voltage drop

24 VDC NAC with a 1.8 A total load; last appliance 250 ft away (one way); 16 AWG stranded cable; appliances listed for 16–33 VDC; the manufacturer says to start from 20.4 V (85% of 24 V, battery at end of discharge).

  1. Loop length: 2 × 250 ft = 500 ft = 0.5 kft.
  2. Loop resistance: 4.99 Ω/kft × 0.5 kft = 2.495 Ω.
  3. VD = 1.8 A × 2.495 Ω ≈ 4.49 V. With the K method: 2 × 12.9 × 1.8 × 250 ÷ 2580 = 4.50 V.
  4. Voltage at the last appliance: 20.4 − 4.49 = 15.91 V → does not comply (below 16 V).
  5. With 14 AWG stranded: 3.14 × 0.5 = 1.57 Ω; VD = 1.8 × 1.57 ≈ 2.83 V; 20.4 − 2.83 = 17.57 V → complies.

The lumped-load method (all current at the end of the circuit) is conservative: if it passes this way, it also passes a point-to-point calculation. The acceptance criterion is the appliance's listed operating range from the manufacturer, not an NFPA 72 number.

Worked example: batteries

Total standby current 0.320 A; total alarm current 2.75 A; non-voice system.

  1. Standby: 0.320 A × 24 h = 7.68 Ah.
  2. Alarm: 2.75 A × (5 ÷ 60) h ≈ 0.229 Ah.
  3. Subtotal: 7.68 + 0.229 ≈ 7.91 Ah.
  4. 25% capacity margin (factor 1.25): 7.91 × 1.25 ≈ 9.89 Ah. With the 20% of earlier editions it would be ≈ 9.49 Ah.
  5. Choose the next commercial battery size the panel charger can recharge (for example, 12 Ah). Two 12-V batteries in series give 24 V with the same Ah capacity.
Battery margin: technical summaries of the 2022 edition of NFPA 72 report that the capacity margin went from 20% to 25% (factor 1.25) to cover battery aging over its service life. Many manufacturer worksheets and older books still use 1.2. On the exam, use the factor the question gives.

EOL, supervision, and typical readings

On Class B, the end-of-line (EOL) resistor goes at the last device on the circuit; the panel watches a small supervisory current (for example, 24 V ÷ 4.7 kΩ ≈ 5.1 mA). The wire must go in and out of each terminal, with no T-taps on conventional circuits, and the wire run must be broken at each terminal rather than looped under it. In standby a NAC supervises with reversed polarity and polarized appliances block that current, so + and − must be respected. Readings with the circuit disconnected from the panel:

ConditionBetween the two conductorsConductor to ground
Normal≈ EOL value + wire (e.g., 4.72 kΩ)Very high (MΩ or OL)
OpenOL (infinite)Very high
Short or closed contactA few ohms (wire only)Very high
Ground faultNormalLow

A wrong EOL (47 kΩ instead of 4.7 kΩ) cuts the supervisory current to one-tenth and the panel may see it as an open. Two equal EOLs in parallel give half the value.

Multimeter and megohmmeter

Alternating current and distribution systems

In the U.S., ac is 60 Hz. Common systems in Ugly's: single-phase 120/240 V (120 V hot to neutral, 240 V between hots), three-phase 208Y/120 V (208 ÷ 1.732 ≈ 120 V to neutral), and 480Y/277 V. The fire alarm panel is normally fed with 120 V ac (hot and neutral; never use the equipment grounding conductor as a return) and supplies 24 V dc to its circuits; the batteries are dc.

Conduit fill (NEC Ch. 9)

CaseMaximumWhere
1 conductor (or 1 multiconductor cable)53%Table 1 + Note 9
2 conductors31%Table 1
More than 2 conductors40%Table 1
Nipple of 24 in. (600 mm) or less between boxes60%Note 4

Same-size conductors: Annex C (Table C.1 = EMT). Mixed sizes: add the areas from Table 5 (14 AWG THHN = 0.0097 in²; 12 AWG THHN = 0.0133 in²) and compare with the matching column of Table 4 (1/2 in. EMT at 40% = 0.122 in²). Round up only if the decimal is 0.8 or more (Note 7).

NFPA 72 does not set a color code for fire alarm conductors: follow the project drawings and specifications.

Common traps

How to find it fast in the printed books

What to tab in your books

SectionWhy
NEC 2020 Ch. 9, Table 8Conductor properties: cmil and dc resistance at 75°C (Ω/kft), solid and stranded
NEC 2020 Ch. 9, Table 1Percent fill: 1 conductor 53%, 2 conductors 31%, over 2: 40%
NEC 2020 Ch. 9, Notes to TablesNote 4 (nipples ≤ 24 in.: 60%), Note 7 (round up at ≥ 0.8), Note 9 (multiconductor cable = 1 conductor)
NEC 2020 Ch. 9, Table 4Conduit and tubing dimensions and areas by type (EMT, PVC, RMC...) at 40/53/31/60%
NEC 2020 Ch. 9, Table 5Dimensions and areas of insulated conductors (THHN, TFFN...)
NEC 2020 Ch. 9, Table 9AC resistance and reactance (do not confuse with Table 8, dc)
NEC 2020 Annex CMaximum number of same-size conductors per raceway (C.1 = EMT)
Ugly's 2020 – Ohm's Law / Power FormulasE, I, R, P formula wheel
Ugly's 2020 – Series and Parallel CircuitsResistance, current, and voltage in series and in parallel
Ugly's 2020 – Voltage Drop CalculationsVD = 2 × K × I × L ÷ CM (1φ) and 1.732 × K × I × L ÷ CM (3φ); K = 12.9 Cu, 21.2 Al
Ugly's 2020 – distribution systems120/240 V single-phase, 208Y/120 V, and 480Y/277 V
NFPA 72-2022 §10.6.7.2.1Secondary capacity: 24 h standby + 5 min alarm (15 min for EVACS)
NFPA 72-2022 §7.2.1Minimum documentation: battery and NAC voltage drop calculations
NFPA 72-2022 Table 14.4.3.2Conductor tests (1 V stray voltage, ground, short, loop resistance) and battery tests
NFPA 72-2022 §10.3Equipment listed, installed per the manufacturer, and compatible
NFPA 72-2022 Ch. 12Circuits and pathways: Class A/B, monitoring for integrity, ground faults

Chapter vocabulary

Voltage (E)
Electrical potential difference, measured in volts (V) with the voltmeter in parallel.
Current (I)
Flow of electric charge, measured in amperes (A) with the ammeter in series.
Resistance (R)
Opposition to current flow, measured in ohms (Ω) with the circuit de-energized.
Ohm's law
The relationship E = I × R between voltage, current, and resistance.
Power (P)
Energy per unit of time, in watts: P = E × I = I² × R = E² ÷ R.
Series circuit
A single current path; resistances add and the current is the same throughout the loop.
Parallel circuit
Several branches with the same voltage; branch currents add (like the appliances on a NAC).
Voltage drop (VD)
Voltage lost in conductor resistance: VD = I × R of the complete loop.
Circular mil (cmil)
Unit of conductor area used in NEC Table 8 (14 AWG = 4110 cmil).
Stranded conductor
Conductor made of several strands; for the same AWG it has slightly more resistance than solid wire.
End-of-line (EOL) resistor
Resistor installed at the end of a Class B circuit so the panel can supervise the wiring.
Supervisory current
Small current that flows through the EOL in standby; if it moves outside its window, the panel indicates trouble.
Open circuit
A break in the current path; the ohmmeter reads OL (infinite).
Short circuit
Low-resistance connection between conductors that bypasses the load or the EOL.
Ground fault
Unintended connection of a circuit conductor to ground (conduit, box, structure).
Stray voltage
Unwanted voltage on installation conductors; NFPA 72 limits it to 1 V ac/dc in acceptance testing.
Megohmmeter (insulation tester)
Instrument that applies a high dc voltage to measure insulation resistance in MΩ.
Multimeter (DMM)
Instrument that measures voltage, current, and resistance depending on the function and inputs selected.
Ampere-hour (Ah)
Battery capacity: the current multiplied by the time the battery can deliver it.
Secondary power supply
Batteries (or another approved source) that keep the system operating when primary power fails.
Quiescent load
Current the system draws in its normal condition, without alarm.
Lumped load
Calculation method that assumes all NAC current is drawn at the last appliance; gives a conservative result.
Conduit fill
Percentage of a raceway's interior area occupied by conductors or cables (NEC Ch. 9, Table 1).
Alternating current (ac)
Current that periodically reverses direction; 60 Hz in the U.S.
Nipple
Short length of conduit (24 in. or less) between boxes or enclosures; may be filled to 60%.

50 practice questions cover this chapter, each with an explanation and the code section. Get lifetime access or try the free practice exam.